Units with hose retrievers, Units with hose retrievers -19, Caution warning – Gasboy Atlas Fuel Systems Installation Manual User Manual
Page 49: Warning

Applicable to Dispensers Rated for E85 Use:
Use only UL-listed TPS PTFE pipe sealant manufactured by SAF-T-LOC International
Corp.
Teflon tape must be used only at the inlet pipe connection.
CAUTION
WARNING
Hose fittings and attachments that are improperly grounded can lead to a spark that may
ignite fuel or its vapors. Explosion or fire can result in severe injury or death. Check
hoses, breakaways, and fittings for proper conductivity after assembly. Consult the
manufacturer’s instructions.
WARNING
DEF Hose Torque
Recommended torque when installing hoses is 40-50 N.m (30-35 ft-lbs). DO NOT OVER
TIGHTEN or damage to the nozzle can occur. Applicable when connecting hoses to the
skid tank, during internal repairs, and nozzle replacement.
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014
Page 6-19
Installing Breakaways, Hoses, Swivels, and Nozzles
Installation
Note: It is important that Teflon tape is not used on threaded connections. Use a UL-approved
sealant suitable for the fuel involved, only where sealing is required (not used for
O-rings). Castings may fracture during assembly or later, if Teflon tape is used.
To install breakaways, hoses, swivels, and nozzles, proceed as follows:
1
Attach the swivel (if used) to the nozzle. Follow the swivel manufacturer’s instructions.
2
Assemble and attach the breakaway whip hose to the swivel or nozzle. Follow the hose
manufacturer’s instructions. For units with hose retrievers, refer to
3
Assemble the breakaway to whip the hose. Follow the breakaway manufacturer’s instructions.
4
Assemble the hose to the breakaway, followed by the unit outlet casting. Follow the
breakaway manufacturer’s instructions. The hose clamp must connect between the breakaway
coupling and pump/dispenser outlet.
Units with Hose Retrievers
For units with hose retrievers, attach the retriever clamp to a long hose that is positioned to
allow maximum extension of the hose, yet prevent a trip hazard. Use hose breakaway
couplings that are installed as per the manufacturer’s instructions
.
WARNING
Failure to position hose clamps correctly may prevent the operation of the breakaway
coupling, resulting in the unit being pulled off an island during a drive-off, with fuel being
spilled. This can result in serious injury or death. Ensure that the hose clamp is installed
between the breakaway coupling and unit outlet casting. This ensures that the
breakaway functions properly.