Installing the Commercial Atlas (9800K) ATC Kits

Page 18

MDE-4431C Gasboy ATC M05819K00X Kits Installation Manual · February 2013

34

Under the shelf (where the IS Barrier Stud is secured), locate the two plugs in the hydraulic
coupling (see

Figure 11

).

Figure 11: Hydraulic Coupling (Probe Assembly Mounting Location)

Probe Assembly

Holes plugged when Probe is not
installed

Adapter

Thermowell Plug

Thermowell

35

When applying SAF-T-LOK

®

TPS Sealant on threads, leave the two threads that

enter the hole first free of sealant to prevent the sealant from entering, and
possibly damaging or inhibiting proper operation of the unit.

CAUTION

Remove the two plugs using an appropriate size Allen-wrench.

36

Coat the Thermowell Threads (BC407) with SAF-T-LOK TPS Sealant and threads into one of
the holes where the plugs were removed in step

35

(see

Figure 11

).

37

Tighten the Thermowell using a proper size wrench and place the Thermowell Plug (235-C)
into the Thermowell.

38

Coat the threads of the Adapter (BC546) with SAF-T-LOK TPS Sealant and turn it into the
other hole where the plugs were removed in step

35

(see

Figure 11

).

39

Coat the threads of the Probe Assembly (W199) with SAF-T-LOK TPS Sealant and turn it into
the Adapter (BC546) mounted in step

38

on

page 26

.