MDE-4431C Gasboy ATC M05819K00X Kits Installation Manual · February 2013
Page 11
Installing the Commercial Atlas (9800K) ATC Kits
3
Peel the protective cover from the Mounting Sponge (on the back of the Polycase Box) and
mount the box as shown in
. Mount about 1-1/2 inches up from shelf (1-1/2-inch
clearance under the shelf).
Figure 3: Mounting the Polycase Box (LP-70)
About
1-1/2 inches
Clearance
4
Locate the two Washers [N23746-01 (mounted to shelf with two screws)] on the two shelves
creating the air gap.
Note: The lower washer location also has a Gasket (N23761-04).
5
Remove the two screws from each washer and remove the washers. Retain the gasket and
screws for use later.
6
Locate the two Conduit Seal Washers (N23760-07) provided in the kit.
7
Place the two Conduit Seal Washers (N23760-07) where the two Washers (N23746-01) were
mounted and place the gasket (saved in step
) under the conduit seal washer on the lower
shelf. Secure washers with screws that were removed in step
.
8
Locate the Dual Intrinsic Safety (IS) Barrier (27913) and Single Probe Connector Assembly
(212AY04) provided in the kit. Remove the nut and washer from the mounting stud on the IS
barrier and slide them off the wires. Retain the nut and washer for use later.