DC Power Technologies Charger Interface Software Manual User Manual
Page 46

45
© 2014 Enatel Motive Power Ltd. Specifications subject to change without prior notice. Errors
exempt. Pictures may be representative, actual products may differ.
AGM-M
AGM-M charging
For charging AGM motive power batteries
Profile type 3
IUUa
Constant current, constant voltage, constant voltage
Var 0 = 100
Stage 1 Current (%)
Stage 1 uses the full nominal rating of the charger
Var 1 = 300
Stage 1 Time Out (minutes)
Calculated on Ahrs to allow for a module being out of service
Var 2 = 2450
Stage 2 Vpc (x1000)
2.45Vpc
Var 3 = 30
Stage 3 Current (%)
Trip point from stage 2 (U) to stage 3 (I)
Var 4 = 0
Stage 3 dv/dt (mV/cell/15mins)
Not used in IUUa profile
Var 5 = 60
Stage 2 Time Out (minutes)
60mins, 1hrs
Var 6 = 2300
Stage 3 Max Vpc (x1000)
2.30Vpc constant voltage temp comp until stage 3 time out
Var 7 = 6
Equalize Current (%)
6%
Var 8 = 120
Equalize Duration (minutes)
120mins
Var 9 = 2450
Equalize Max Vpc (x1000)
2.45Vpc
Var 10 = 300
Stage 3 Time Out (minutes)
300mins, 5hrs
Var 11 = 30
Auto Equalize After (minutes)
Auto EQ starts after being connected to the charger for this time
Var 12 = 4
Equalize Lockout (hours)
4 hours
Var 13 = 30
Temp Comp Factor
Compensation of -3mV/cell/ºC, Centre Temperature 25ºC
Var 14 = 0
Sulphate Detect
Auto sulphate detect function active 1=yes 0=no
Var 15 = 0
Auto Equalize
Auto equalize function active 1=yes 0=no
AGM-R
AGM-R charging
Charging reserve batteries or using as a power supply
Profile type 4
IUa
Constant voltage current limited profile with a time off function
Var 0 = 100
Stage 1 Current (%)
Stage 1 uses the full nominal rating of the charger
Var 1 = 720
Stage 1 Time Out (minutes)
720mins, 12 hours
Var 2 = 2350
Stage 2 Vpc (x1000)
2.35Vpc
Var 3 = 0
Stage 3 Current (%)
Not used in IUa profile
Var 4 = 0
Stage 3 dv/dt (mV/cell/15mins)
Not used in IUa profile
Var 5 = 0
Stage 2 Time Out (minutes)
Not used in IUa profile
Var 6 = 0
Stage 3 Max Vpc (x1000)
Not used in IUa profile
Var 7 = 0
Equalize Current (%)
Not used in IUa profile
Var 8 = 0
Equalize Duration (minutes)
Not used in IUa profile
Var 9 = 0
Equalize Max Vpc (x1000)
Not used in IUa profile
Var 10 = 0
Stage 3 Time Out (minutes)
Not used in IUa profile
Var 11 = 0
Auto Equalize After (minutes)
Not used in IUa profile
Var 12 = 0
Equalize Lockout (hours)
Not used in IUa profile
Var 13 = 0
Temp Comp Factor
Not used in IUa profile
Var 14 = 0
Sulphate Detect
Not used in IUa profile
Var 15 = 0
Auto Equalize
Not used in IUa profile