AGM-M

AGM-M charging

For charging AGM motive power batteries

Profile type 3

IUUa

Constant current, constant voltage, constant voltage

Var 0 = 100

Stage 1 Current (%)

Stage 1 uses the full nominal rating of the charger

Var 1 = 300

Stage 1 Time Out (minutes)

Calculated on Ahrs to allow for a module being out of service

Var 2 = 2450

Stage 2 Vpc (x1000)

2.45Vpc

Var 3 = 30

Stage 3 Current (%)

Trip point from stage 2 (U) to stage 3 (I)

Var 4 = 0

Stage 3 dv/dt (mV/cell/15mins)

Not used in IUUa profile

Var 5 = 60

Stage 2 Time Out (minutes)

60mins, 1hrs

Var 6 = 2300

Stage 3 Max Vpc (x1000)

2.30Vpc constant voltage temp comp until stage 3 time out

Var 7 = 6

Equalize Current (%)

6%

Var 8 = 120

Equalize Duration (minutes)

120mins

Var 9 = 2450

Equalize Max Vpc (x1000)

2.45Vpc

Var 10 = 300

Stage 3 Time Out (minutes)

300mins, 5hrs

Var 11 = 30

Auto Equalize After (minutes)

Auto EQ starts after being connected to the charger for this time

Var 12 = 4

Equalize Lockout (hours)

4 hours

Var 13 = 30

Temp Comp Factor

Compensation of -3mV/cell/ºC, Centre Temperature 25ºC

Var 14 = 0

Sulphate Detect

Auto sulphate detect function active 1=yes 0=no

Var 15 = 0

Auto Equalize

Auto equalize function active 1=yes 0=no

AGM-R

AGM-R charging

Charging reserve batteries or using as a power supply

Profile type 4

IUa

Constant voltage current limited profile with a time off function

Var 0 = 100

Stage 1 Current (%)

Stage 1 uses the full nominal rating of the charger

Var 1 = 720

Stage 1 Time Out (minutes)

720mins, 12 hours

Var 2 = 2350

Stage 2 Vpc (x1000)

2.35Vpc

Var 3 = 0

Stage 3 Current (%)

Not used in IUa profile

Var 4 = 0

Stage 3 dv/dt (mV/cell/15mins)

Not used in IUa profile

Var 5 = 0

Stage 2 Time Out (minutes)

Not used in IUa profile

Var 6 = 0

Stage 3 Max Vpc (x1000)

Not used in IUa profile

Var 7 = 0

Equalize Current (%)

Not used in IUa profile

Var 8 = 0

Equalize Duration (minutes)

Not used in IUa profile

Var 9 = 0

Equalize Max Vpc (x1000)

Not used in IUa profile

Var 10 = 0

Stage 3 Time Out (minutes)

Not used in IUa profile

Var 11 = 0

Auto Equalize After (minutes)

Not used in IUa profile

Var 12 = 0

Equalize Lockout (hours)

Not used in IUa profile

Var 13 = 0

Temp Comp Factor

Not used in IUa profile

Var 14 = 0

Sulphate Detect

Not used in IUa profile

Var 15 = 0

Auto Equalize

Not used in IUa profile