2.15. Controller Settings Tab
Provides full control over advanced charger settings and parameters.
Settings:
Voltage Regulation
Regulate voltage at charger level
instead of module level. Default:
Enabled
Monitor Current Share
Regulate current at charger level
instead of module level. Default:
Enabled.
Current Shunt Measurement
Measure current output using FS5 & 9
charger shunt(s). Default: Enabled
Minimum Module Voltage
Minimum nominal voltage the charger
can be set to. Default: 25V
Maximum Module Voltage
Maximum nominal voltage charger can
be configured to. Default: 66V
Maximum Module Current
Maximum current per charger module.
Default: 66V
Urgent Module Fail Count
Number of failed modules required
before an urgent alarm is triggered,
stopping the current charge cycle.
Default: 2
Automatic Module Shutdown
Intelligently disable modules to ensure
charger operates at the highest
efficiency or to optimise power factor.
Fuse Blown Threshold
Maximum Voltage allowed across the
DC fuses before the output fuse alarm
is set Default: 0.7V
Cable Resistivity
DC cable resistance value. Default:
20nΩ.m
Configuration Alarm Threshold
Percentage of nominal current that
must be achieved by the charger within
a given time, before the charger
triggers the configuration error alarm.
Default: 95%
Zero Current Threshold
Minimum amount of current possible
before an urgent alarm is triggered and
charge terminated. Default: 0.4A
Start-up Battery Temp Limit
Charger will not start if this value is
exceeded at start-up. Default:
55°C/131°F
Charging Battery Temp Limit
Charger will trigger an urgent alarm
and terminate charge if this value is
exceeded. Default: 60°C/131°F
dI/dt Threshold
Maximum allowable increase in current
during the finishing charge. Default:
20A
Temperature Compensation
Temperature compensation when an
external temp sensor or battery
module is fitted. Default: Disabled
APC Mode/BMID Mode
Force charger into APC mode: Single,
Dual or Disabled. Default: Disabled
Battery Status Indicator
Dedicate two relays to triggering a
remote charge status indicator (relays
1&3).
Relay Alarm Mode
Dedicate two relays to an alarm
trigger. Specify the alarm type and
relay in the Alarm Configuration tab.
Desulphation Minimum Voltage