2.15. Controller Settings Tab

Provides full control over advanced charger settings and parameters.

Settings:

Voltage Regulation

Regulate voltage at charger level
instead of module level. Default:
Enabled

Monitor Current Share

Regulate current at charger level
instead of module level. Default:
Enabled.

Current Shunt Measurement

Measure current output using FS5 & 9
charger shunt(s). Default: Enabled

Minimum Module Voltage

Minimum nominal voltage the charger
can be set to. Default: 25V

Maximum Module Voltage

Maximum nominal voltage charger can
be configured to. Default: 66V

Maximum Module Current

Maximum current per charger module.
Default: 66V

Urgent Module Fail Count

Number of failed modules required
before an urgent alarm is triggered,
stopping the current charge cycle.
Default: 2

Automatic Module Shutdown

Intelligently disable modules to ensure
charger operates at the highest
efficiency or to optimise power factor.

Fuse Blown Threshold

Maximum Voltage allowed across the
DC fuses before the output fuse alarm
is set Default: 0.7V

Cable Resistivity

DC cable resistance value. Default:
20nΩ.m

Configuration Alarm Threshold

Percentage of nominal current that
must be achieved by the charger within
a given time, before the charger
triggers the configuration error alarm.
Default: 95%

Zero Current Threshold

Minimum amount of current possible
before an urgent alarm is triggered and
charge terminated. Default: 0.4A

Start-up Battery Temp Limit

Charger will not start if this value is
exceeded at start-up. Default:
55°C/131°F

Charging Battery Temp Limit

Charger will trigger an urgent alarm
and terminate charge if this value is
exceeded. Default: 60°C/131°F

dI/dt Threshold

Maximum allowable increase in current
during the finishing charge. Default:
20A

Temperature Compensation

Temperature compensation when an
external temp sensor or battery
module is fitted. Default: Disabled

APC Mode/BMID Mode

Force charger into APC mode: Single,
Dual or Disabled. Default: Disabled

Battery Status Indicator

Dedicate two relays to triggering a
remote charge status indicator (relays
1&3).

Relay Alarm Mode

Dedicate two relays to an alarm
trigger. Specify the alarm type and
relay in the Alarm Configuration tab.

Desulphation Minimum Voltage