6. Alarms
6.1. Charger Related Alarms
Main Switch
Shows the status of the front panel
start/stop switch. Default: Urgent
Inlet Filter
Can give a warning as to when the
inlet filter needs servicing.
Default:Disabled
Low Mains
Indicates non-critical variation in the
input mains voltage. May also indicate
an overloaded charger module.
Default:Non-Urgent
Mains Fail
A mains supply loss situation and the
charge cannot proceed. Default:
Urgent
Non-Urgent Rectifier Fail
The charger is operating but a charger
module has stopped, causing
redundancy to be lost. Reduced power
output and longer charge time as a
result. Default:Non-Urgent
Urgent Rectifier Fail
If the number of power modules not
providing output equals or exceeds the
setting for urgent module count in
Charger Interface monitor tab then the
charger will stop. If the urgent module
count is set to one then the charger is
configured without redundancy and a
single fault will stop the charge.
Default: Urgent
Module Over Temperature
Normally related to a blocked filter,
restricted exhaust air or installation in
an inappropriate location. Default:
Urgent
Configuration Error
Charger cannot meet the target current
required by the controller even with all
fitted power modules operating. The
configuration does not meet the limits
set for a 10A or 15A mains input
hardware limited charger. Default:
Urgent
Output Fuse
Typically blown output fuses caused by
connecting a reverse polarity battery to
the charger. Check all cells for a
reversed cable connection. After
replacing a battery or charger cable
always check the polarity before
plugging the battery into the charger.
Default: Urgent
No Output Current
Charger is not providing the expected
output current. Generally related to a
premature disconnection of the
battery, but also could be an
incorrectly inserted power module.
Default: Urgent
Monitor ADC Fail
Internal checks on the MPC board
indicate potential problems. MPC board
should be tested and/or replaced.
Default: Urgent
APC Communications Fail
The battery module has failed to
communicate with the charger.
Default: Urgent
APC Incorrect Voltage
Charger cannot produce the voltage
required by the battery module.
Default: Urgent
APC Unknown Charger
Charger cannot find the required profile
required by the battery module.
Default: Urgent
APC Water Level Low
For battery module equipped batteries,
indicates the Electrolyte Sensor has
detected a low level of electrolyte.
Default:Non-Urgent
APC Voltage Imbalance
For battery module equipped batteries,
indicates the midpoint voltage varies
from nominal by more than 0.5V.
Battery module will schedule an
equalize charge to rectify this
variation. Default:Non-Urgent