2.13. Alarm Configuration Tab
Requires Advanced Access.
The various charger alarms are, by
default, organised into Urgent and
Non-Urgent levels. The level of
the alarm determines the charger’s
response to that alarm. In addition
to alarm levels, alarms can also be
configured to activate one of two
relays, or activate the in-charger
audible beep.
Read/Write
Click Read to view each of the lists
stored in the charger, Write to
save any changes to a list back to
the charger.
Lists
Six lists allow addition and removal
of alarms from each category as
labelled at the top of each list.
Right-clicking in a list allows a new
alarm to be added to that list.
Right-clicking on a selected alarm
in a list allows the option to remove
that alarm from the list.
Refer to Section 6: Alarms for a list
of the default alarm lists.
Alarm Configuration Lists:
Alarm Log
Alarms listed here will appear in
the alarm log.
Urgent Alarm
Alarms categorized as Urgent
terminate the charge cycle and
alarm and charge logs are flagged
with the event. Notification is by a
front panel display message and
alternate
flashing
Ready
and
Charging LEDs.
Non-Urgent Alarm
Alarms categorized as Non-Urgent
allow the charge cycle to continue.
Flags alarm log. Notification is by
front panel display and flashing red
Charging LED.
Alarm Relays 1 & 2
Alarms selected to activate an on-
board
relay
for
external
accessories.
Buzzer
Alarms selected to produce an
audible tone from the charger when
triggered, until the alarm condition
is cleared or the charge cycle is
complete.