Attery, Elated, Larms – DC Power Technologies Charger Interface Software Manual User Manual
Page 35: Battery related alarms

34
© 2014 Enatel Motive Power Ltd. Specifications subject to change without prior notice. Errors
exempt. Pictures may be representative, actual products may differ.
6.3. Battery Related Alarms
Over Discharged Battery
Battery is still under 1.9Vpc after 30
seconds of charge. Indicates a faulty
battery that needs investigation.
Default: Urgent
Deeply Discharged Battery
Battery initially is under 1.9Vpc but
recovers within 30 seconds of the
charge cycle start. This alarm normally
occurs when a battery is unplugged
from the lift truck and immediately
plugged into the charger. Default:Non-
Urgent
Sulphated Battery
Battery fails to complete a de-
sulphation profile applied by the
charger correctly and generally means
that the battery requires attention.
Default: Urgent
Incorrect Battery
Battery is inappropriate for the
configuration of the charger and cannot
be charged without reconfiguring the
charger to suit the battery. Default:
Urgent
Bulk Charge Timeout
Battery has exceeded the maximum
time allowed for the initial constant
current bulk charge phase. Could
indicate a faulty battery or the charger
configuration is not correct for the size
of battery. May need additional charger
modules added to the charger. Default:
Urgent
Finishing Charge Timeout
Battery has exceeded the maximum
time allowed for the finishing part of
the charge cycle. Common with new
batteries with less than 10 charge
cycles. If the alarm occurs regularly,
investigation is advised and possible
adjustment of the charger or service of
the battery. Default:Non-Urgent
Battery Disconnected
Battery has been unplugged before
charge cycle has completed. This can
damage the battery connector and
increase risks of ignition of battery
charge gasses. If the battery needs to
be disconnected mid cycle, the charger
must be first set to STOP. A partial
charge cycle will be logged. Default:
Urgent
Reversed Battery
A battery with positive and negative
cables reversed has been connected to
the charger. Generally this will also
cause an output fuse alarm and the
need to replace the charger output
fuse(s). Batteries should always first
be checked for correct polarity BEFORE
plugging onto the lift truck or a
charger. Default: Urgent
Minimum dV/dt
Change in battery voltage over time.
Alarm occurs when the change in
voltage exceeds the value set in the
profile settings. This alarm also
indicates the termination of a
successful charge. Default:Non-Urgent
Maximum Cell Voltage
Occurs when the voltage per cell
exceeds the value set in the profile
settings. Typically 2.7V per cell for lead
acid batteries. Default:Non-Urgent
Batt Over Temp – Start
Occurs when the battery temperature
measured before a charge profile starts
exceeds the value set in the controller
settings. This alarm will not allow the
charge profile to continue. Default:
Urgent
Batt Over Temp - Charge
Occurs when the battery temperature
measured during a charge profile
exceeds the value set in the controller
settings. This alarm will allow the
charge profile to complete.
Default:Non-Urgent
+dI/dt
Occurs when the measured current in
the constant voltage stage is rising
instead of falling. This alarm will
terminate the charge profile. Default:
Urgent
Minimum Current
Occurs when using a IU profile and the
current in the constant voltage stage
falls below the value set in the profile
settings. This alarm will not stop a
profile and is considered normal for
some types of batteries. Default:Non-
Urgent
EQ/Refresh Timeout
Occurs when the time threshold in a
given stage of the equalize profile has
been exceeded. This alarm will
terminate the equalize charge but is
not considered an urgent alarm.
Default:Non-Urgent