AGM-Ch
Champion
Suitable for manufacturer specific motive power batteries
Profile type 1
IUIa
Constant current, constant voltage, constant current
Var 0 = 100
Stage 1 Current (%)
Typically 0.15xBattery C5 rating, Max 0.2xC5
Var 1 = 390
Stage 1 Time Out (minutes)
390mins, 6.5 hours
Var 2 = 2370
Stage 2 Vpc (x1000)
2.37Vpc temp compensated
Var 3 = 19
Stage 3 Current (%)
19%
Var 4 = 3
Stage 3 dv/dt (mV/cell/15mins)
Setting for the dv/dt termination
Var 5 = 210
Stage 2 Time Out (minutes)
210mins, 3.5hrs, safety for a combined stage 2+3
Var 6 = 2550
Stage 3 Max Vpc (x1000)
2.55Vpc, charge stops if reached
Var 7 = 10
Equalize Current (%)
10%
Var 8 = 120
Equalize Duration (minutes)
120mins
Var 9 = 2550
Equalize Max Vpc (x1000)
2.55Vpc
Var 10 = 0
Stage 3 Time Out (minutes)
Champion only use a combined timeout for stage2+3
Var 11 = 30
Auto Equalize After (minutes)
Auto Eq starts after being connected to the charger for this time
Var 12 = 4
Equalize Lockout (hours)
var12=4 Equalize lockout (hours) 4 hours
Var 13 = 30
Temp Comp Factor
Compensation of -3mV/cell/ºC, Centre Temperature 25ºC
Var 14 = 0
Sulphate Detect
Auto sulphate detect function active 1=yes 0=no
Var 15 = 0
Auto Equalize
Auto equalize function active 1=yes 0=no
ConstCurr
Constant current charging
Commissioning charge of a flooded motive power battery
Profile type 2
Ia
Constant current until time or max volts limits are reached
Var 0 = 30
Stage 1 Current (%)
Uses 30% of the rated based on nom current set to 0.2xC5
Var 1 = 300
Stage 1 Time Out (minutes)
300mins 5hrs, stops provided it doesn't hit max volts first
Var 2 = 2700
Stage 2 Vpc (x1000)
Shutdown limit, Hits max volts and stops
Var 3 = 0
Stage 3 Current (%)
Not used in Ia profile
Var 4 = 0
Stage 3 dv/dt (mV/cell/15mins)
Not used in Ia profile
Var 5 = 0
Stage 2 Time Out (minutes)
Not used in Ia profile
Var 6 = 0
Stage 3 Max Vpc (x1000)
Not used in Ia profile
Var 7 = 0
Equalize Current (%)
Not used in Ia profile
Var 8 = 0
Equalize Duration (minutes)
Not used in Ia profile
Var 9 = 0
Equalize Max Vpc (x1000)
Not used in Ia profile
Var 10 = 0
Stage 3 Time Out (minutes)
Not used in Ia profile
Var 11 = 0
Auto Equalize After (minutes)
Not used in Ia profile
Var 12 = 0
Equalize Lockout (hours)
Not used in Ia profile
Var 13 = 0
Temp Comp Factor
Not used in Ia profile
Var 14 = 0
Sulphate Detect
Not used in Ia profile
Var 15 = 0
Auto Equalize
Not used in Ia profile