6.5. BMM Alarms
EEPROM Fail
The module has detected an
unrecoverable internal error which may
cause functionality and logging
failures. Module should be replaced as
soon as possible.
State of Charge Low
Battery charge is at or below the
defined threshold. Thresholds are set
in the Battery Module Settings tab.
Default threshold is 20% of the rated
capacity.
State of Health Low
Battery State of Health is calculated
from the change in State of Charge
over the expected number of charge
cycles for the life of the battery.
Default threshold is 20%.
Temperature Low
Battery temperature has reached the
minimum threshold. Thresholds are set
in the Battery Module Settings tab.
Default threshold is 5°C/41°F.
Temperature High
Battery temperature has reached the
maximum threshold. Thresholds are
set in the Battery Module Settings tab.
Default threshold is 55°C/131°F.
Cell Imbalance
Voltage difference between each half of
the battery (positive post to midpoint
and midpoint to negative post) must
be below the set threshold. Thresholds
are set in the Battery Module Settings
tab. Default threshold is 0.5V.
Electrolyte Level
The electrolyte sensor (if fitted) has
detected a low electrolyte level. This
alarm can flag the battery to receive a
top-up from an auto watering kit if
fitted.