Harge, Rofile, Efault – DC Power Technologies Charger Interface Software Manual User Manual
Page 44: Arameters, Charge profile default parameters
43
© 2014 Enatel Motive Power Ltd. Specifications subject to change without prior notice. Errors
exempt. Pictures may be representative, actual products may differ.
7.3. Charge Profile Default Parameters
PROFILES
DEFINITION
COMMENTS/DEFAULT SETTINGS
Flooded
Flooded lead acid Cell
Normal flooded traction batteries
Profile type 1
IUIa
Constant current, constant voltage, constant current
Var 0 = 100
Stage 1 Current (%)
Allowable range to AS 2548 is 0.12 to 0.3xBattery C5 rating
Var 1 = 390
Stage 1 Time Out (minutes)
Calculated on Ahrs to allow for a module being out of service
Var 2 = 2400
Stage 2 Vpc (x1000)
2.4Vpc temp compensated
Var 3 = 25
Stage 3 Current (%)
30% max 20% min, typically 25%
Var 4 = 3
Stage 3 dv/dt (mV/cell/15mins)
Setting for the dv/dt termination
Var 5 = 330
Stage 2 Time Out (minutes)
330mins combined stage 2+3 timeout
Var 6 = 2700
Stage 3 Max Vpc (x1000)
2.7Vpc, charge stopped when reached
Var 7 = 12
Equalize Current (%)
Typically 12% >20% gives max voltage trips during equalize
Var 8 = 120
Equalize Duration (minutes)
Equalize Duration (minutes) 120mins
Var 9 = 2700
Equalize Max Vpc (x1000)
2.7Vpc
Var 10 = 0
Stage 3 Time Out (minutes)
Flooded uses a combined timeout for stage2+3
Var 11 = 30
Auto Equalize After (minutes)
Auto EQ starts after being connected to the charger for this time
Var 12 = 4
Equalize Lockout (hours)
Lockout inhibit after charge complete for a manual equalize cycle
Var 13 = 30
Temp Comp Factor
Compensation of -3mV/cell/ºC, Centre Temperature 25degC
Var 14 = 0
Sulphate Detect
Sulphate Detect Auto sulphate detect function active 1=yes 0=no
Var 15 = 0
Auto Equalize
Auto Equalize Auto equalize function active
GEL
GEL cell
Suitable for Evolution GEL cell batteries
Profile type 1
IUIa
Constant current, constant voltage, constant current
Var 0 = 100
Stage 1 Current (%)
Recommended setting is 0.17xBattery C5 rating, Max is 0.2xC5
Var 1 = 360
Stage 1 Time Out (minutes)
Calculated on Ahrs to allow for a module being out of service
Var 2 = 2350
Stage 2 Vpc (x1000)
2.35Vpc temp compensated
Var 3 = 6
Stage 3 Current (%)
6%
Var 4 = 3
Stage 3 dv/dt (mV/cell/15mins)
Setting for the dv/dt termination
Var 5 = 270
Stage 2 Time Out (minutes)
270mins, 4.5hrs
Var 6 = 2600
Stage 3 Max Vpc (x1000)
2.6Vpc, charge stops if reached
Var 7 = 3
Equalize Current (%)
3%
Var 8 = 120
Equalize Duration (minutes)
120mins, 2hrs
Var 9 = 260
Equalize Max Vpc (x1000)
2.6
Var 10 = 180
Stage 3 Time Out (minutes)
180mins, 3hrs
Var 11 = 30
Auto Equalize After (minutes)
Auto Eq starts after being connected to the charger for this time
Var 12 = 4
Equalize Lockout (hours)
Lockout inhibit after charge complete for a manual equalize cycle
Var 13 = 30
Temp Comp Factor
Compensation of -3mV/cell/ºC, Centre Temperature 25degC
Var 14 = 0
Sulphate Detect
Auto sulphate detect function active 1=yes 0=no
Var 15 = 0
Auto Equalize
Auto Equalize Auto equalize function active 1=yes 0=no