BayTech MRP units 2012 User Manual
Page 9
![background image](https://www.manualsdir.com/files/774070/content/doc009.png)
Page
9
Circuit Breaker
Unit Processors
Depending on if the unit has circuit breakers, in the case of power overload, the circuit breaker
automatically trips. Determine the cause of the tripped circuit breaker, correct the problem then reset the
circuit breaker by depressing the circuit breaker switch. If an overload condition occurs, the
MRP/MMP/MSP/MDP status menu is still accessible. If all circuits are closed, the circuit breaker status
menu will indicate “On.” If the circuit breaker is tripped, the circuit breaker status will indicate “Off.” If
no power cord is attached to the “IN” receptacle, the circuit breaker status will indicate “Off”, indicating
there is no power available to the “OUT” receptacle.
208V/48A Rated Model:
(60A Maximum Over current protection Device).
208V/40A Rated Model:
(50A Maximum Over current protection Device).
208V/24A Rated Model:
(30A Maximum Over current protection Device).
208V/16A Rated Model:
(20A Maximum Over current protection Device)
208V/12A Rated Model:
(15A Maximum Over current protection Device)
400V/16A Rated Model:
(20A Maximum Over current protection Device)
120V/24A Rated Model:
(30A Maximum Over current protection Device)
120V/16A Rated Model:
(20A Maximum Over current protection Device)
The unit controller has two processors, Ethernet and Outlet processors. Both processors are flash
upgradable via Ethernet port. Power strips with only a Serial port must be connected to a Master unit or
Baytech Data Switch to upgrade the Outlet Controller. You may contact Baytech Technical Support for the
latest firmware.
Each Outlet Modules has a processor that communicates with the Outlet Controller. This processor cannot
be upgraded in the field. If an upgrade is needed, Baytech Technical Support will be contacted you.