STATUS
This shows the current status
of all circuit to the circuit
breaker level. It shows Circuit
Groups, True RMS Current,
Peak RMS Current, True RMS
Voltage, Average Power, and
Volt-Amps. Status also shows
whether the outlets are on, off,
or locked.
Unit ID: MRP10
Total kW-h: 0
-------------------------------------------------------------------------------
| Circuit | True RMS | Peak RMS | True RMS | Average | Volt- |
| Group | Current | Current | Voltage | Power | Amps |
-------------------------------------------------------------------------------
| Circuit C1 | 0.0 Amps | 0.7 Amps | 202.2 Volts | 0 Watts | 4 VA |
| Circuit C2 | 0.0 Amps | 0.0 Amps | 204.1 Volts | 0 Watts | 4 VA |
| Circuit C3 | 0.2 Amps | 0.5 Amps | 202.9 Volts | 0 Watts | 52 VA |
| Circuit C4 | 0.6 Amps | 0.9 Amps | 202.3 Volts | 50 Watts | 123 VA |
| Circuit C5 | 1.3 Amps | 1.8 Amps | 203.7 Volts | 92 Watts | 265 VA |
| Circuit C6 | 0.9 Amps | 1.4 Amps | 206.0 Volts | 74 Watts | 199 VA |
-------------------------------------------------------------------------------
Int. Temp: 95.9 F Ext. 1: 72.3 F : 31.5% RH Ext. 2: 71.1 F
1)...Outlet 1 : On 2)...Outlet 2 : On
3)...Outlet 3 : On 4)...Outlet 4 : On
5)...(RIGHT) Outlet : On 6)...Outlet 6 : On
7)...Outlet 7 : On 8)...Outlet 8 : On
9)...Outlet 9 : On 10)...Outlet 10 : On
11)...Outlet 11 : On 12)...(LEFT) Outlet 1 : On
13)...Outlet 13 : On 14)...Outlet 14 : On
15)...Outlet 15 : On 16)...Outlet 16 : On
17)...Outlet 17 : On 18)...Outlet 18 : On
19)...Outlet 19 : On 20)...Outlet 20 : On
21)...Outlet 21 : On 22)...Outlet 22 : On
23)...Outlet 23 : On 24)...Outlet 24 : On
25)...Outlet 25 : On 26)...Outlet 26 : On
27)...Outlet 27 : On 28)...Outlet 28 : On
29)...Outlet 29 : On 30)...Outlet 30 : On
A unit with less than (6)
circuit breakers will show the
current status of the breakers
and all circuit module level. It
shows Circuit Groups, True
RMS Current, Peak RMS
Current, True RMS Voltage,
Average Power, and Volt-
Amps. Status also shows
whether the outlets are on, off,
or locked
Total kW-h: 10
------------------------------------------
| Circuit | True RMS | Peak RMS |
| Breaker | Current | Current |
------------------------------------------
| CKT1 | 0.3 Amps | 0.6 Amps |
| CKT2 | 0.6 Amps | 0.7 Amps |
-------------------------------------------------------------------------------
| Circuit | True RMS | Peak RMS | True RMS | Average | Volt- |
| Group | Current | Current | Voltage | Power | Amps |
-------------------------------------------------------------------------------
| Circuit M1 | 0.2 Amps | 0.3 Amps | 128.2 Volts | 10 Watts | 27 VA |
| Circuit M2 | 0.0 Amps | 0.1 Amps | 218.9 Volts | 0 Watts | 3 VA |
| Circuit M3 | 0.1 Amps | 0.1 Amps | 219.6 Volts | 0 Watts | 31 VA |
| Circuit M4 | 0.2 Amps | 0.2 Amps | 221.7 Volts | 0 Watts | 44 VA |
| Circuit M5 | 0.2 Amps | 0.2 Amps | 223.0 Volts | 0 Watts | 53 VA |
| Circuit M6 | 0.2 Amps | 0.2 Amps | 222.7 Volts | 0 Watts | 52 VA |
-------------------------------------------------------------------------------
Int. Temp: 89.6 F
Switch 1: Open 2: Open
1)...MOD 1 Outlet 1 : On 2)...MOD 1 Outlet 2 : On
3)...MOD 1 Outlet 3 : On 4)...MOD 1 Outlet 4 : On
5)...MOD 1 Outlet 5 : On 6)...MOD 1 Outlet 6 : On
7)...MOD 2 Outlet 1 : On 8)...MOD 2 Outlet 2 : On
9)...MOD 2 Outlet 3 : On 10)...MOD 2 Outlet 4 : On
11)...MOD 2 Outlet 5 : On 12)...MOD 3 Outlet 1 : On
13)...MOD 3 Outlet 2 : On 14)...MOD 3 Outlet 3 : On
15)...MOD 3 Outlet 4 : On 16)...MOD 3 Outlet 5 : On
17)...MOD 3 Outlet 6 : On 18)...MOD 4 Outlet 1 : On
19)...MOD 4 Outlet 2 : On 20)...MOD 4 Outlet 3 : On
21)...MOD 4 Outlet 4 : On 22)...MOD 4 Outlet 5 : On
23)...MOD 5 Outlet 1 : On 24)...MOD 5 Outlet 2 : On
25)...MOD 5 Outlet 3 : On 26)...MOD 5 Outlet 4 : On
27)...MOD 5 Outlet 5 : On 28)...MOD 5 Outlet 6 : On
29)...MOD 6 Outlet 1 : On 30)...MOD 6 Outlet 2 : On
31)...MOD 6 Outlet 3 : On 32)...MOD 6 Outlet 4 : On
33)...MOD 6 Outlet 5 : On