BayTech MRP units 2012 User Manual
Page 55

Page
55
Power Factor Threshold Menu
 
 
 
 
 
Individual Units
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Breaker List for device 1, MRP-27 
Ckt PF Threshold (%) Pwr Threshold (W) 
 1 100 10 
 2 100 10 
 3 100 10 
 4 100 10 
 5 100 10 
 6 100 10 
 
Enter Request :1
Parameters to control generation of SNMP traps based on
circuit Power/VA power factor and minimum power level 
 
Sel M/P Identifier Circuits Outlets 
1 2/1 MRP27 6 24 
2 All Circuits/Outlets - Power Factor Threshold 
3 All Circuits/Outlets - Power Threshold 
 
Enter Request :1 
 
Circuit Power Factor Thresholds....1 
Outlet Power Factor Thresholds.....2 
 
Enter Request :1
Select 1),
displays either Circuit or
Outlet Power Factor (PF)
Unit displays breaker list of circuits. 
Select the Circuit number to change 
the threshold values 
Select 9), from the RPC Management Menu, displays the unit’s power efficiency on the web 
page and through SNMP. The user sets a minimum power level that will send an SNMP trap to the 
SNMP Manager. The smaller the power factor, less than (1), more current is needed (wasted) to do 
the same amount work 
M/P = Module port, 
Identifier = Unit Id, 
Circuits = number of circuits on unit. 
Outlets = number of unit outlets. 
Select 1), displays current Power 
Factor (PF) and Power Threshold 
settings for each individual unit 
circuit. 
Breaker Circuit Threshold Menu 
Device 1, Breaker Circuit 1 
Efficiency Threshold: 100, Power Threshold: 10 
 
 Power/VA Power Factor Threshold....1 
 Minimum Power Threshold............2 
 
Enter Request :1
Unit displays the Breaker Circuit 
Threshold Menu with circuit breaker 
number and current values. 
 
Select 1), changes the Power Factor 
Threshold level. Enter a per cent value 
(%). Factory Default is (0%). 
Power/VA ratio threshold as a percent, between 0 and 100, 
inclusive. Power factors below this value will generate an SNMP 
trap, if enabled and power is above minimum power threshold. A 
value of 0 disables threshold. 
 
 Enter threshold value: 
NOTE: The Power Factor Threshold SNMP alarm is sent only if both respective values drop 
below the Power Factor Threshold and Power Threshold at the same time. 