Power Factor Threshold Menu 





Individual Units 






































Breaker List for device 1, MRP-27
Ckt PF Threshold (%) Pwr Threshold (W)
1 100 10
2 100 10
3 100 10
4 100 10
5 100 10
6 100 10

Enter Request :1

Parameters to control generation of SNMP traps based on
circuit Power/VA power factor and minimum power level

Sel M/P Identifier Circuits Outlets
1 2/1 MRP27 6 24
2 All Circuits/Outlets - Power Factor Threshold
3 All Circuits/Outlets - Power Threshold

Enter Request :1

Circuit Power Factor Thresholds....1
Outlet Power Factor Thresholds.....2

Enter Request :1

Select 1),

displays either Circuit or

Outlet Power Factor (PF)

Unit displays breaker list of circuits.
Select the Circuit number to change
the threshold values

Select 9), from the RPC Management Menu, displays the unit’s power efficiency on the web
page and through SNMP. The user sets a minimum power level that will send an SNMP trap to the
SNMP Manager. The smaller the power factor, less than (1), more current is needed (wasted) to do
the same amount work

M/P = Module port,
Identifier = Unit Id,
Circuits = number of circuits on unit.
Outlets = number of unit outlets.

Select 1), displays current Power
Factor (PF) and Power Threshold
settings for each individual unit
circuit.

Breaker Circuit Threshold Menu
Device 1, Breaker Circuit 1
Efficiency Threshold: 100, Power Threshold: 10

Power/VA Power Factor Threshold....1
Minimum Power Threshold............2

Enter Request :1

Unit displays the Breaker Circuit
Threshold Menu with circuit breaker
number and current values.

Select 1), changes the Power Factor
Threshold level. Enter a per cent value
(%). Factory Default is (0%).

Power/VA ratio threshold as a percent, between 0 and 100,
inclusive. Power factors below this value will generate an SNMP
trap, if enabled and power is above minimum power threshold. A
value of 0 disables threshold.

Enter threshold value:

NOTE: The Power Factor Threshold SNMP alarm is sent only if both respective values drop
below the Power Factor Threshold and Power Threshold at the same time.