BayTech MRP units 2012 User Manual

Page 29

background image

Page

29 









Enable/Disable Status Menu  




















Change Unit ID 





Change Alarm Threshold   














Unit ID: MRP
------------------------------------------
| Outlet | True RMS | Peak RMS |
| Group | Current | Current |
------------------------------------------
| Outlet 1-8 | 0.2 Amps | 0.2 Amps |
------------------------------------------
Internal Temperature: 73.4 F

Switch 1: Open 2: Open

1)...Outlet 1 : On
2)...Outlet 2 : On
3)...Outlet 3 : On
4)...Outlet 4 : On
5)...Outlet 5 : On
6)...Outlet 6 : On
7)...Outlet 7 : On
8)...Outlet 8 : On

Type Help for a list of commands

MRP>

Select 5), from the Outlet Control Menu changes the Unit ID.
The unit will display the following:

The default ID is the unit’s number, in this case MRP20

Current Unit ID: MRP20
Modify (Y/N)? y
Enter New Unit ID: Cab7_Rack1 MRP20

Type “Y” to enable the confirmation option, or type “N” to disable. If the
confirmation feature is enabled and a command is sent to TURN ON, TURN
OFF, OR REBOOT a receptacle, the unit will ask to confirm the command.
For example, the command “ON 3” is sent, and the unit will display the
following:
If this feature is disabled, the unit will perform the command and redisplay
the previous menu.

Turn On Outlet 3? (Y/N)

Select 4), from the Outlet Control Menu enables
the Status menu. The unit will display the option to
change the current status: Default setting is
Enabled.

If this feature is disabled, only the prompt appears,
else the following status menu appears.

Enable Status Menu (Y/N)? y

Select 6), from the Outlet Control Menu allows the user to set the current level for the internal alarm
to sound. This setting is only available on units with current monitoring circuitry.

1)...Circuit Breaker Alarms
2)...Module/Group Circuit Breaker Alarms

If the number of circuit breakers equals the number of
modules, the unit will display the following:

Circuit C1buzzer alarm value : 12.0 Amps
Modify (Y/N)? y
Enter: 2.0

Type “N” to keep the current value or type “Y” to change the
value and enter the new value, followed by ‘Enter’ and the
unit will display next circuit group.

Circuit C2 buzzer alarm value : 7.0 Amps
Modify (Y/N)? n

If the number of circuit breakers DOES NOT equals the
number of modules, the unit will display the following: