All Circuits/Outlets ­ Power Factor Threshold  




















All Circuits/Outlets ­ Power Threshold 








Outlet Circuit Threshold Menu
Device 1, Outlet 1
Efficiency Threshold: 100, Power Threshold: 10

Power/VA Power Factor Threshold....1
Minimum Power Threshold............2

Enter Request :

Unit displays the Outlet Circuit
Threshold Menu with Device Outlet
number and current values.

Select 2), changes the Minimum Power
Threshold level. Enter a value. Factory
Default is (50w).

Minimum power required to generate an SNMP power factor
trap if power factor is below threshold.

Enter threshold value:

This option allows user to set all circuits and outlets to the same Power Factor Threshold levels.
(MMX) refers to the metered-outlet modular- series. Default Value = (0%)

Power/VA ratio threshold as a percent, between 0 and 100, inclusive.
Power factors below this value will generate an SNMP trap, if enabled and
power is

above

minimum power threshold. A value of 0 disables threshold.


Value will be applied to all circuits and outlets (MMX units).

Enter threshold value:

This option allows user to set all circuits and outlets to the same Power Threshold levels. (MMX) refers
to the metered-outlet modular series. Default Value = (50w)

Minimum power required to generate an SNMP power factor
trap if power factor is below threshold.

Value will be applied to all circuits and outlets (MMX units).

Enter threshold value:

Setting all Power/VA Efficiency Thresholds to 80%

Power Factor Threshold Menu

Parameters to control generation of SNMP traps based on
circuit Power/VA power factor and minimum power level

Sel M/P Identifier Cks #Outs
1 2/1 MRP-27 6 24
2 All

Circuits

/Outlets - Power Factor Threshold

3 All Circuits/Outlets - Power Threshold

Enter Request :

The unit responds with
message stating the
Thresholds were set to
the new value and
displays the Menu.