California Instruments

Revision H

18

User Manual

MX Series CTSH Compliance Test System


Minimal R

sce

Admissible individual

harmonic current I

n

/I

1

*

%

Admissible harmonic current

distortion factors

%

I

5

I

7

I

11

I

13

THD

PWHD

33

10.7

7.2

3.1

2

13

22

66

14

9

5

3

16

25

120

19

12

7

4

22

28

250

31

20

12

7

37

38

350

40

25

15

10

48

46

Note 1- The relative value of even harmonics shall not exceed 16/n %.

Note 2 - Linear interpolation between successive R

sce

values is permitted.

*

I

1

= rated fundamental current; I

n

= harmonic current component.

Table 2-3: Stage 2 current emission limits for balanced three-phase equipment

Minimal R

sce

Admissible individual

harmonic current I

n

/I

1

*

%

Admissible harmonic current

distortion factors

%

I

5

I

7

I

11

I

1 3

THD

PWHD

33

10.7

7.2

3.1

2

13

18

120

40

25

15

10

48

46

Note 1- The relative value of even harmonics shall not exceed 16/n %.

Note 2 - Linear interpolation between successive R

sce

values is permitted.

*

I

1

= rated fundamental current; I

n

= harmonic current component.

Table 2-4: Stage 2 current emission limits for balanced three-phase equipment

with given phase angle conditions

Stage 3:

No specific limits apply for stage 3 connection equipment. The connection of the equipment must be
negotiated with the local utility. The CTS system will provide test data which documents the amount of
current harmonics emissions produced by the EUT. No limits are applied in this mode so there is no pass
or fail test result in this case.