beautypg.com

9 clock and lock mode (-lkm/-lks option) – AMETEK Compact IX 2253 User Manual

Page 48

background image

User Manual

2253i / 2253iX

AMETEK California

Instruments

48

3.9 Clock and Lock Mode (-LKM/-LKS Option)

Clock and lock mode operation of two or more iX AC power sources is available only if the –LKM and
–LKS options have been installed at the factory. With these options installed, it is possible to lock an
auxiliary unit (-LKS) to a master unit (-LKM). The master unit controls the frequency. This
configuration can be used to create multiphase power systems such as split-phase or three phases.
The auxiliary unit must be set to external clock mode from the Control screen. See section 4.2.5.

Two BNC connectors are provided on the rear panel of the iX model for clock and lock mode. Both
need to be connected between the master and auxiliary unit. On the master unit (-LKM), both are
outputs. On the auxiliary unit (-LKS), both are inputs. Do not connect these BNC’s between two
master units (-LKM’s) or damage to the unit could result.

GND NEUT LINE

CLOCK

LOCK

Master power source (-LKM)

Auxiliary power source (-LKS)

AC INPUT POWER

CLOCK LOCK

CLOCK LOCK

COMMON
NEUTRAL

Figure 3-6: Clock and Lock Connections

Refer to Figure 3-6 for the required connections between the –LKM and –LKS units. The example is
shown for two units, one master, one auxiliary. More than one auxiliary can be used to create
additional phase outputs. In this case, the BNC cables can be daisy chained using BNC T connectors.

WARNING:

DO NOT CONNECT THE AC OUTPUTS OF THE –LKM AND –LKS UNITS TOGETHER.
CLOCK AND LOCK OUTPUTS CANNOT BE PARALLELED TO OBTAIN HIGHER
OUTPUT CURRENTS.

Do not use clock and lock mode to obtain higher power capability on the same phase(s).

The frequency of the auxiliary unit will track that of the master. The output phase angle of phase 1/A
will be locked to the auxiliary unit as well to within 3°. Phase B and C of each unit will be referenced to
phase A of the same unit. This allows split phase or multi-phase configurations to be created.