Modular Block System: Burner Management
6-51
Programming guidelines
•
ENBL
The enable
ENBL of SB154 must be supplied to the AND-operation
before the global input
ERR or to the AND-operation before the global
input
CHAI of SB152 “Burner: Start and operator elements”. The
decision to use
ERR or CHAI depends on the user and the respective
standards regarding error reaction.
ERR:
If an error is present, a controlled shutdown occurs when
AuSt = 1 with restart.
CHAI:
If an error is present, a safety shutdown occurs.
A programming example can be found in Chapter 8 under “Managing
enables”.
•
Dir1 and Dir2
Driving one flap: the drive must be driven in one direction only i.e.
Dir1
and
Dir2 must not be driven simultaneously.