Output parameters, Function, Error messages – Pilz PSS SB FT, Basic license User Manual
Page 129

Modular Block System: Burner Management
6-85
Output parameters
•
ENBL:
Enable flag bit
ENBL = 1: this function is fault-free
(refer also to the Programming guidelines)
•
RDY:
Step sequence output
If a block step is activated, the corresponding bit is set in the
output parameter
RDY.
•
IGNI:
Ignition transformer
IGNI = 1: switch on ignition transformer
•
VAV1:
Safety valve (valve 1)
VAV1 = 1: open safety valve
•
VAV2:
Pilot valve (valve 2)
VAV2 = 1: open pilot valve
•
RUN:
RUN = 1: result of the step carried out, pilot flame should be
established. This status must be monitored by SB150 “Flame
monitoring” (supply
RUN from SB 158 to RUN from SB150).
•
FLAI:
Driving the pilot flame monitor
Note: supply the output parameter
FLAI from SB158 to the
input parameter
MONI from SB150 for monitoring the pilot
flame.
FLAI = 1: Pilot flame monitoring
Function
• Monitoring the ignition process
• Driving the safety and pilot valves
• Selecting means of ignition: manual or automatic
• Driving SB150 FLAME_M for pilot flame monitoring
• Reaction to the system enable of SB152 “Burner: Start and operator
elements”
Error messages
Any fault that is detected will be stored statically in the corresponding error
data word (
SSNR) of DB015 (1st data block).