Modular Block System: Burner Management

Standard Function Blocks

SB157: Several ignition attempts

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte-constants KB001 ... KB200
(further information about the

SSNR can be found in the

sections “Administration data blocks DB015, DB016 and
DB017” and “Input parameter

SSNR” in chapter 5).

Value of DW0000/DB015 = 0: no error present.

SyOK:

General plant status (system OK)
Note: supply the output parameter

ENBL from SB152 to the

input parameter

SyOK of SB157.

SyOK = 1: no error
SyOK = 0: error in the system, leads to a shutdown.

BIT0:

First step for ignition
(see Programming guidelines)

BIT3:

Step “Flame stabilising time ended; flame established”
(see Programming guidelines)

FLAs:

Global signal input of the flame monitor
(see Programming guidelines)

ITRY:

Permitted number of direct successive ignition attempts.

SB157

SB157

IGNI_TRY

B - SSNR
X - SyOK
X - BIT0
X - BIT3
X - FLAs
B - ITRY
X - STEP

W - T_V

Z - T

RDY - X