Blocks required, Standard function blocks, Sb153 – Pilz PSS SB FT, Basic license User Manual
Page 86
6-42
Modular Block System: Burner Management
Standard Function Blocks
- Bit 02: Switch time for the change in position is exceeded.
Remedy: check the switch time
T_V for the contact(s) and reset
the error.
- Bit 03:
DirO and DirC driven simultaneously
Remedy: Only drive in one direction and reset the error. If
neither limit switch is operated, the drive direction must be re-
selected.
- Bit 04: Feasibility check: neither limit switch operated.
Remedy: Check contacts and reset the error. Subsequently if
neither limit switch is operated, the drive direction must be re-
selected.
- Bit 05: Feasibility check: both limit switches operated.
Remedy: check contacts and reset error.
- Bit 06: Reset button not operated
Remedy: Press reset button
- Bit 07: A new drive direction selected
Remedy: Create a positve edge at
DirC or DirO
• Error messages on the CPU-display
- E001: Parameter errors
The
SSNR does not lie withn the limits 1 ... 200. The incorrect
SSNR is stated in DB015/DW0000 (refer also to the section
“Administration data blocks DB015, DB016 and DB017 in
chapter 5).
- E007: Invalid time value for
T_V
Blocks required
• DB002:
Will be made available when the configurator is called up
• DB015:
Administration data block
DB015 must consist of its totla length of 1024 data words and
have Read/Write status (see the section “Administration data
blocks DB015, DB016 and DB017” in chapter 5).
• OB101:
To call up SB153
SB153