Modular Block System: Burner Management
6-65
L
M90.00
. VAV1 SB156
O
M90.02
. VAV1 SB158
=
A2.00
. VAV1
L
M90.01
. VAV3 SB156
O
M90.03
. VAV3 SB159
=
A2.01
. VAV3
• Shutdown
If
SyOK = 0 or if a fault occurs (see error messages), a shutdown follows:
° No enable
→
ENBL = 0
° Seal check not active
→
RDY = 0
° Close safety valve
→
VAV1 = 0
° Close main valve
→
VAV3 = 0
° Close exhaust valve
→
VAV4 = 0
° Test output
→
GP- = 0
° Test output
→
GP+ = 0
SB159
RUN
B - SSNR
B - NEXT
X - SyOK
ENBL - X
RDY - B
VAV3 - X - M
90.03
.VAV3 SB159
REGL - X
RUN - X
FLAM - X
SB158
IGNITION
B - SSNR
B - NEXT
X - SyOK
X - MANU
X - S_IG
ENBL - X
RDY - B
IGNI - X
VAV1 - X - M
90.02
.VAV1 SB158
VAV2 - X
RUN - X
FLAI - X