Standard function blocks, Sb158 – Pilz PSS SB FT, Basic license User Manual
Page 134

6-90
Modular Block System: Burner Management
Standard Function Blocks
-
NEXT, Bit 2 = 1:
Open pilot valve
° Enable
→
ENBL = 1
° Ignition step 3 is active
→
RDY, Bit 2 = 1
° Ignition transformer switched on
→
IGNI = 1
° Safety valve open
→
VAV1 = 1
° Open pilot valve
→
VAV2 = 1
° Pilot flame not established
→
RUN = 0
° Do not monitor pilot flame
→
FLAI = 0
-
NEXT, Bit 3 = 1:
Pilot flame established
° Enable
→
ENBL = 1
° Ignition step 4 is active
→
RDY, Bit 3 = 1
° Ignition transformer switched on
→
IGNI = 1
° Safety valve open
→
VAV1 = 1
° Pilot valve open
→
VAV2 = 1
° Pilot flame established
→
RUN = 1
° Monitor pilot flame
→
FLAI = 1
-
NEXT, Bit 4 = 1:
Switch off pilot transformer
° Enable
→
ENBL = 1
° Ignition step 5 is active
→
RDY, Bit 4 = 1
° Switch off ignition transformer
→
IGNI = 0
° Safety valve open
→
VAV1 = 1
° Pilot valve open
→
VAV2 = 1
° Pilot flame established
→
RUN = 1
° Monitor pilot flame
→
FLAI = 1
-
NEXT, Bit 5 = 1:
Close pilot valve
° Enable
→
ENBL = 1
° Ignition step 6 is active
→
RDY, Bit 5 = 1
SB158