Standard Function Blocks

SB159: Run

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte-constants KB001 ... KB200
(further information about the

SSNR can be found in the

sections “Administration data blocks DB015, DB016 and
DB017” and “Input parameter

SSNR” in chapter 5).

Value of DW0000/DB015 = 0: no error present

NEXT:

Sequence input
Bits 0...3 of the input byte represent a processing step in the
block. By setting a bit the corresponding step in the block is
started.

SyOK:

General plant status (system OK)
Note: supply the output parameter

ENBL from SB152 to the

input parameter

SyOK of SB159.

SyOK = 1: no error
SyOK = 0: error in the system, leads to a shutdown

Output parameters

ENBL:

Enable flag bit
ENBL = 1: this function is fault-free
(refer also to Programming guidelines)

RDY:

Sequence output
If a block step is activated, the corresponding bit is set in the
output parameter

RDY.

SB159

SB159

RUN

B - SSNR
B - NEXT
X - SyOK

ENBL - X

RDY - B

VAV3 - X

REGL - X

RUN - X

FLAM - X