Standard function blocks – Pilz PSS SB FT, Basic license User Manual
Page 158

6-114
Modular Block System: Burner Management
Standard Function Blocks
Block
Connection required
Reason
SB157
Perform
AND-operation
Flame fault
on all
ENBL from SB150
→
evaluation
FLAs (SB157)
Bit 0,
NEXT (SB158)
→
Detecting the step
BIT0 (SB157)
“Switch on ignition
transformer”
Bit 3,
NEXT (SB158)
→
Detecting the step
BIT3 (SB157)
“Pilot flame
established”
Pulse at
RDY (SB157)
→
Immediate further ignition
must set the step flag
NEXT attempt after a failure
of the previous step from
step “Switch on ignition
transformer”
STEP (SB152)
→
Burner start detection and
STEP (SB149, SB157)
resetting sequence
SB158
ENBL (SB152)
→
Valve seal when a
SyOK (SB158)
shutdown occurs
RUN (SB158)
→
For pilot flame
RUN (SB150)
monitoring
FLAI (SB158)
→
For pilot flame
MONI (SB150)
monitoring
Triggered pulse via neg. edge
Fault leads to a normal
from
ENBL (SB158)
shutdown (when
AuSt = 1
→
AND-connection before
with restart)
ERR (SB152)
or
Triggered pulse via neg. edge
Fault leads to a safety
from
ENBL (SB158)
shutdown
→
AND-connection before
CHAI (SB152)