Modular Block System: Burner Management

Standard Function Blocks

Block

Connection required

Reason

SB157

Perform

AND-operation

Flame fault

on all

ENBL from SB150

evaluation

FLAs (SB157)

Bit 0,

NEXT (SB158)

Detecting the step

BIT0 (SB157)

“Switch on ignition
transformer”

Bit 3,

NEXT (SB158)

Detecting the step

BIT3 (SB157)

“Pilot flame

established”
Pulse at

RDY (SB157)

Immediate further ignition

must set the step flag

NEXT attempt after a failure

of the previous step from
step “Switch on ignition
transformer”

STEP (SB152)

Burner start detection and

STEP (SB149, SB157)

resetting sequence

SB158

ENBL (SB152)

Valve seal when a

SyOK (SB158)

shutdown occurs

RUN (SB158)

For pilot flame

RUN (SB150)

monitoring

FLAI (SB158)

For pilot flame

MONI (SB150)

monitoring

Triggered pulse via neg. edge

Fault leads to a normal

from

ENBL (SB158)

shutdown (when

AuSt = 1

AND-connection before

with restart)

ERR (SB152)
or
Triggered pulse via neg. edge

Fault leads to a safety

from

ENBL (SB158)

shutdown

AND-connection before

CHAI (SB152)