6-38

Modular Block System: Burner Management

Standard Function Blocks

SB152

Automatic restart after air deficiency

When

AuSt = 1 and FTRY = 1, SB152 sets its ENBL and STEP output

immediately if the input conditions are fulfilled after air pressure failure
i.e.

AirP = 0

If correct air pressure is present again, monitoring can be activated with

NEXT

and then the next step can be carried out. With each burner start-up, a pulse
is created at the

STEP output with which all SB149 blocks and SB157 are

reset.

Spurious signals

No irregularities with a safety sequence failure.
ENBL= 1 only after a reset, a de-energised
monitor sequence and start pulse. geschlosse-