Output parameters, Function, Error messages – Pilz PSS SB FT, Basic license User Manual
Page 67

Modular Block System: Burner Management
6-23
Output parameters
ENBL: Enable flag bit
ENBL = 1: the signal at the N/C contact S1 is fault-free
(refer also to Programming guidelines)
Function
Spurious signals at the monitored input (e.g. a pressure monitor) cancels
the enable after a set time.
If the N/C contact functions without fault, SB151 sets the enable
ENBL. If
interference occurs, the enable is cancelled after a set time period. Short,
fleeting interferences, for example, pressure swings after the valve has
opened will have no effect on the enable.
Error messages
Any fault that is detected will be stored statically in the corresponding error
data word (SSNR) of DB015 (1st data block).
• Error messages in DB015
- Bit 09: Suppression time has elapsed, the signal is spurious
Remedy: check contact
S1 and if AuSt = 0, press the reset
button
RSET.
- Bit 14: Reset button
RSET pressed continuously or pressed too soon.
Remedy: Release reset button and press again.
- Bit 15: Signal is fault-free, but the error which occurred was not reset
(
RSET missing)
Remedy: press the reset button
RSET.
• Error Messages on the CPU-display
- E001: Parameter errors
The
SSNR does not lie within the limits of 1 ... 200. The
incorrect
SSNR is stated in DB015/DW0000 (refer also to the
section “Administration data blocks DB015, DB016 and DB017”
in chapter 5).
- E007: Invalid time value for
T_V