Error messages, Blocks required – Pilz PSS SB FT, Basic license User Manual
Page 47

Modular Block System: Burner Management
6-3
• Each SB149 of this sequence waits for the ready signal from the
previous step and for the step enabling conditions to be fulfilled, before
it is active.
• Step monitoring time: a step provess can be monitored for a specific
time
• Time delay: a function process can be limited to a certain time, or the
process can be started after a specific time.
Error messages
• Error messages in DB015
None
• Error messages on the CPU-display
E006:
Parameter errors- the time base
W_BA or D_BA does not lie
within the permitted range 0 to 4. The incorrect value will be
entered in DR0 (data byte right) of the administration data block
DB015.
Blocks required
• DB002:
Will be made available when the configurator is called up
• DB015:
Administration data block
DB015 must consist of its total length of 1024 data words and
have Read/Write access (see section “Administration data
blocks DB015, DB016 and DB017” in chapter 5).
• OB101:
To call up SB149
• SB149:
STEP
• SB255:
To call up the operating system