Managing enables, Examples – Pilz PSS SB FT, Basic license User Manual

Page 166

background image

8-2

Examples

Modular Block System: Burner Management

INFORMATION
This section contains examples which should help when creating the pro-
gram for your plant applications.

The examples should be viewed as a model. The given flags have been
selected at random from example to example, so they may have a different
meaning in each instance.

Managing enables

The enable

ENBL must be treated according to each standard function

block.

ENBL from the flame monitor block SB150

Perform an AND-operation of all enables from SB150 in the user pro-
gram after they have been called up. The result of this bit operation must
be supplied to the input parameter

FLAs from SB152 “Burner: Start and

operator elements”.

ENBL/FG of the standard function block with RSET or EIN (e.g.
SB061 E-STOP Cat. 4) as input parameter

In the user program perform an AND-operation of all the enables from
the SBs, which have the possibility to reset, after they have been called
up.

The result of this bit-operation must be supplied to the AND-operation
before the global input

ERR or to the AND-operation before the global

input

CHAI from SB152 “Burner: Start and operator elements”. The

decision to use

ERR or CHAI depends on the user and the respective

standards regarding error reaction.