Modular Block System: Burner Management
Standard Function Blocks
Spurious signals at
NEXT input
Only when Bit 0 to Bit 5 from
NEXT is carried out in ascending order is the
RDY-bit sample changed step-by-step.
Individual steps, i.e.
NEXT bits on the input cannot be missed out. Returns
(loop backs) are not possible. If this is not maintained the enable is
cancelled in every case. The enable is triggered again when all
NEXT bits
are reset. A new cycle is started exclusively when the Bit 0 from
NEXT is
set.