Sb151: transient suppression, Sb152: burner: start and operator elements, Appendix – Pilz PSS SB FT, Basic license User Manual
Page 186

9-4
Appendix
Modular Block System: Burner Management
SB151: Transient suppression
Version
Date
CRC
1.0
18.08.97
0F69
1.1
05.02.99
5710
Changes from Version 1.0 to Version 1.1
Internal start-up has been improved: Evaluation of the negative edge from
S1 in cases where SB 151 has not been called up in each cycle and
immediately after a cold start or reset, even though the block is required for
the application.
SB152: Burner: start and operator elements
Version
Date
CRC
1.0
09.12.97
2859
1.1
26.03.98
FF21
STOP
1.2
12.08.98
C491
Changes from Version 1.0 to Version 1.1
• Addition of input parameter
D_C.
- This parameter contains the number of cycles for the delayed enable of
SB 152 after the PSS has started-up. The delayed enable is required so
that the flame monitors can reach a defined position without a fault lock-
out occurring.
- The input parameter D_C replaces internally DL 1021 in DB 015.
• Addition of the output parameter
STEP.
- This parameter signals burner start-up for the duration of a cycle.
- The output parameter
STEP replaces internally Bit 0 from DW 1021 in
DB 015.
- This allows you to operate several work cycles (e.g. burners) on one
PSS.
• When starting after triggering the STOP-Signal, the signal to reset
the sequence (STEP) is set for the duration of one cycle.