6-50
Modular Block System: Burner Management
Standard Function Blocks
- Bit 03:
Dir1 and Dir2 driven simultaneously
Remedy: Only drive in one direction and reset the error in the
start position (
Pos1 operated, Pos2 not operated, Dir2 = 0).
- Bit 04: Feasibility check: neither limit switch operated
Remedy: Check contacts and reset the error in the start position
(
Pos1 operated, Pos2 not operated, Dir2 = 0).
- Bit 05: Feasibility check: both limit switches operated
Remedy: Check contacts and reset the error in the start position
(
Pos1 operated, Pos2 not operated, Dir2 = 0).
- Bit 06: Reset button not operated
Remedy: Press reset button
- Bit 07: Valve start position is missing
Remedy: Check contacts and reset the error in the start position
(
Pos1 operated, Pos2 not operated, Dir2 = 0).
• Error messages on the CPU-display
- E 001: Parameter errors
The
SSNR does not lie within the limits 1 ... 200. The incorrect
SSNR is stated in DB015/DW0000 (refer also to the section
“Administration data blocks DB015, DB016 and DB017” in
chapter 5).
- E007: Invalid time value for
T_V
Blocks required
• DB002:
Will be made available when the configurator is called up
• DB015:
Administration data block
DB015 must consist of its total length of 1024 data words and
have Read/Write status (refer also to the section “Administrati-
on data blocks DB015, DB016 and DB017” in chapter 5).
• OB101:
To call up SB154
• SB152:
BR_START for the error reaction
• SB154:
VALVE
• SB255:
To call up the operating system
SB154