Programming guidelines – Pilz PSS SB FT, Basic license User Manual
Page 87

Modular Block System: Burner Management
6-43
• SB152:
BR_START for error reaction
• SB153:
FLAP
• SB255:
To call up the operating system
Programming guidelines
•
ENBL
The
ENBL of SB153 must be supplied to the AND-operation before the
global input
ERR or to the AND-operation before the global input CHAI of
SB152 “Burner: Start and operator elements”. The decision to use
ERR
or
CHAI depends on the user and the respective standards regarding
error reaction.
ERR:
If an error is present, a controlled shutdown occurs when
AuSt = 1 with restart
CHAI:
If an error is present a safety shutdown occurs
A programming example can be found in Chapter 8 under “Managing
enables.
• Driving the air dampers
During burner start-up the air dampers must be driven by SB153. After a
control enable, position monitoring is no longer required and the air
damper motors can be drive directly without SB153.
A programming example can be found in the section “driving the Air
Dampers” in Chapter 8.
•
DirO and DirC
Driving one flap: the drive must be driven in one direction only i.e.
DirO
and
DirC must not be driven simultaneously.