Modular Block System: Burner Management
Temporary flag range in MBS blocks
Internally, MBS blocks use the flags in the range M 64.00 ... M69.31 as
temporary flags.
NOTICE
We recommend the following:
• Do not use flags from the temporary flag range for your own applications.
Malfunctions may occur if you use the temporary flag range M64.00 ...
M69.31 for your own applications.
• If it is absolutely necessary to use this flag range, under no
circumstances should you use the flags:
- in alarm OBs
- as input parameters for standard function blocks
- as output parameters for standard function blocks
- as global parameters
Output parameter ENBL
Many standard function blocks have an enable output ENBL. This output
parameter indicates the enable status of a standard function block. The
enable status results from the standard function block’s check of the
inputs.
ENBL
= 1: No error found,
the function is enabled
ENBL
= 0: An error has been found,
the function is not enabled.