Modular Block System: Burner Management

Standard Function Blocks

Loss of minimum pressure signal as valve

VAV1 is incorrectly seated

SB156

If the min-pressure monitor responds within the seal/pressure check the
ENBL output is cancelled.
The

ENBL signal causes an error message in an overriding function: on

the basis of this, the signal

SyOK is also reset continuously.

After an acknowledgement reset, i.e.

SyOK was set again, the seal/

pressure check can begin again.
Since

SyOK was held at "1" by this test, the ENBL signal will be set

immediately after a program cycle.