Frequency protection, Underfrequency, Overfrequency – Winco DGC-2020 User Manual
Page 76

4-26
DGC-2020 BESTCOMSPlus Software
9400200990 Rev B
Figure 4-24. BESTCOMSPlus Voltage Protection Settings
A
Undervoltage Pickup: Adjustable from 70 to 576 Vac in 1 Vac increments.
B
Undervoltage Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments.
C
Undervoltage Alarm Configuration: None, Alarm, or Prealarm.
D
Undervoltage Inhibit Frequency: Adjustable from 20 to 400 Hz in 1 Hz increments.
E
Undervoltage Low Line Scale Factor: Adjustable from 0 to 3.000 in increments of 0.001.
F
Overvoltage Pickup: Adjustable from 70 to 576 Vac in 1 Vac increments.
G
Overvoltage Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments.
H
Overvoltage Alarm Configuration: None, Alarm, or Prealarm.
I
Overvoltage Low Line Scale Factor: Adjustable from 0 to 3.000 in increments of 0.001.
J
Phase Imbalance Pickup: Adjustable from 5 to 100 Vac in 1 Vac increments.
K
Phase Imbalance Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments.
L
Phase Imbalance Alarm Configuration: None, Alarm, or Prealarm.
Frequency Protection
Two sets of frequency protection settings are provided: one for underfrequency (81U) and one for
overfrequency (81O).
Underfrequency
An underfrequency condition is annunciated when the generator frequency decreases below the 81U
pickup setting
for the duration of the 81U activation delay setting
. An underfrequency annunciation can
be user-selected to trigger a pre-alarm
(warning) or alarm
C
(shutdown). An underfrequency annunciation
can also be user-configured to close a programmable output.
A voltage-based inhibit setting
prevents an 81U trip from occurring during an underfrequency condition
associated with system startup.
Overfrequency
When the generator frequency increases above the 81O pickup setting
for the duration of the 81O
activation delay setting
, an overfrequency condition is annunciated. An overfrequency annunciation can
be user-selected to trigger a pre-alarm
(warning) or alarm (shutdown). An overfrequency condition can
also be user configured to close a programmable output.