Winco DGC-2020 User Manual
Page 104

5-6
DGC-2020 BESTlogic+ Programmable
9400200990 Rev B
Name Description
Symbol
59TRIP
TRUE when the 59 overvoltage is in a TRIP condition. Connect to
another logic block input.
81TRIP
TRUE when the 81 frequency is in a TRIP condition. Connect to another
logic block input.
47TRIP
(Optional)
TRUE when the 47 phase imbalance is in a TRIP condition. Connect to
another logic block input.
51TRIP
(Optional)
TRUE when the 51 overcurrent is in a TRIP condition. Connect to
another logic block input.
GENBRK
Used to control the generator breaker. Connect the inputs and outputs to
inputs and outputs of other logic blocks.
MAINSBRK
Used to control the mains breaker. Connect the inputs and outputs to
inputs and outputs of other logic blocks. (This item is only available when
the Mains Breaker Hardware in configured on the Breaker Hardware
screen via the Breaker Management tree branch.)
AVR
Can be connected to inputs of other logic blocks. When the AVR is being
raised, the Raise output is TRUE. When being lowered, the Lower output
is TRUE.
GOVR
Can be connected to inputs of other logic blocks. When the Governor is
being raised, the Raise output is TRUE. When being lowered, the Lower
output is TRUE.
LOGICALM
When this input is TRUE, the DGC-2020 goes into an Alarm condition.