Winco DGC-2020 User Manual
Page 185

9400200990 Rev B
DGC-2020 Modbus
™ Communication
B-27
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
43752
Remote Start
0-1
R W
A value of 1 will invoke the Remote
Start
43754
Remote Stop
0-1
R W
A value of 1 will invoke the Remote
Stop
43756
Run Mode
0-1
R W
A value of 1 will invoke the Run Mode
43758
Off Mode
0-1
R W
A value of 1 will invoke the Off Mode
43760
Auto Mode
0-1
R W
A value of 1 will invoke the Auto Mode
43762 RESERVED
43764
Gen Breaker Open
0-1
R W
A value of 1 will open the Gen Breaker
43766
Gen Breaker Close
0-1
R W
A value of 1 will close the Gen Breaker
43768
Mains Breaker Open
0-1
R W
A value of 1 will open the Mains
43770
Mains Breaker Close
0-1
R W
A value of 1 will close the Mains
43772 RESERVED
43774
Virtual Input 1 Close
0-1
R W
A value of 1 will close the Virtual Input 1
Switch
43776
Virtual Input 1 Open
0-1
R W
A value of 1 will open the Virtual Input 1
Switch
43778
Virtual Input 2 Close
0-1
R W
A value of 1 will close the Virtual Input 2
Switch
43780
Virtual Input 2 Open
0-1
R W
A value of 1 will open the Virtual Input 2
Switch
43782
Virtual Input 3 Close
0-1
R W
A value of 1 will close the Virtual Input 3
Switch
43784
Virtual Input 3 Open
0-1
R W
A value of 1 will open the Virtual Input 3
Switch
43786
Virtual Input 4 Close
0-1
R W
A value of 1 will close the Virtual Input 4
Switch
43788
Virtual Input 4 Open
0-1
R W
A value of 1 will open the Virtual Input 4
Switch
43790-998 FUTURE
USE
PROTECTION
44000-34 RESERVED
44036-248 FUTURE
USE
44250
3 Phase Overcurrent Pickup
18-118 1A
90-7750 5A
R W
(Sec Amps / 100) in increments of 1
44252
3 Phase Overcurrent Time Dial
0-99
R W
(Units / 10) in increments of 1
44254
3 Phase Overcurrent Curve
0-16
R W
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
44256
3 Phase Overcurrent Alarm
Configuration
0-2 R
W
0 = None
1 = Alarm
2 = Pre-Alarm
44258
1 Phase Overcurrent Pickup
18-118 1A
90-7750 5A
R W
(Sec Amps / 100) in increments of 1
44260
1 Phase Overcurrent Time Dial
0-99
R W
(Units / 10) in increments of 1