9400200990 Rev B
DGC-2020 Modbus
™ Communication
B-9
Table B-3. Legacy Parameter Table
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
40001-18 RESERVED
PARAMETER SETTINGS
40019 Emergency
Stop
0-1
W
0 =Off
1 =Stop
40020
Remote Start / Stop
0-1
W
0 =Stop
1 =Start
40021-22 RESERVED
SYSTEM PARAMETERS
40023
Default Generator Connection
0-2
R W
0=3ph L-L
1=3ph L-N
2=1ph A-B
40024
NFPA Level
0-2
R W
0=Off
1=Level 1
2=Level 2
40025 RESERVED
40026
Rated Engine RPM
750-3600
R W
RPM
40027
Number Flywheel Teeth
50-500
R W
40028
Genset KW Rating
25-9999
R W
KWatt
40029
No Load Cool Down Time
0-60
R W
Minutes
GENERATOR PT PRIMARY
40030
Voltage(a)
1-15000
R W
DP
VoltsAC x10000
40031 Voltage(b)
R
W DP
VoltsAC
GENERATOR PT SECONDARY
40032
Voltage
1-480
R W
VoltsAC
GENERATOR CT PRIMARY
40033
Current
1-5000
R W
AmpsAC
LOW FUEL ALARM
40034 Enable
0-1
R
W
0 =Off
1 =On
40035
Threshold
2-50
R W
% Full Tank
LOW FUEL PRE-ALARM
40036 Enable
0-1
R
W
0 =Off
1 =On
40037
Threshold
10-100
R W
% Full Tank
LOW COOLANT TEMP PRE-ALARM
40038 Enable
0-1
R
W
0 =Off
1 =On
40039
Threshold
40-100
R W
Degrees F
BATTERY OVERVOLTAGE PRE-ALARM
40040 Enable
0-1
R
W
0 =Off
1 =On
40041 RESERVED
MAINTENANCE INTERVAL PRE-ALARM
40042 Enable
0-1
R
W
0 =Off
1 =On
40043 Threshold
0-5000
R
W
Hours
ENGINE KW OVERLOAD PRE-ALARM
40044 Enable
0-1
R
W
0 =Off
1 =On
40045
Threshold
95-140
R W
% of Rated
HIGH COOLANT TEMP PRE-ALARM
40046 Enable
0-1
R
W
0 =Off
1 =On
40047
Threshold
100-280
R W
Degrees F
LOW OIL PRESSURE PRE-ALARM
40048 Enable
0-1
R
W
0 =Off
1 =On