Programmable inputs, Configurable inputs, Are illustrated in figure 4-17 – Winco DGC-2020 User Manual
Page 67

9400200990 Rev B
DGC-2020 BESTCOMSPlus Software
4-17
Figure 4-17. BESTCOMSPlus Sensing Transformers Parameters
A
Gen PT Primary Volts: Adjustable from 1 to 9999 Vac in 1 Vac increments.
B
Gen PT Secondary Volts: Adjustable from 1 to 480 Vac in 1 Vac increments.
C
Gen CT Primary Amps: Adjustable from 1 to 5,000 Aac in 1 Aac increments.
D
Bus PT Primary Volts: Adjustable from 1 to 9999 Vac in 1 Vac increments.
E
Bus PT Secondary Volts: Adjustable from 1 to 480 Vac in 1 Vac increments.
PROGRAMMABLE INPUTS
DGC-2020 contact inputs can be assigned to trigger various functions and, when triggered, annunciate an
alarm or pre-alarm. A user-assigned label can be assigned to each input to make identification easier.
The description of these settings is organized as follows:
• Configurable
inputs
• Programmable
Functions
Configurable Inputs
Each of the 16 contact inputs can be independently configured to annunciate an alarm or pre-alarm
when the input senses a contact closure. A user-adjustable time delay
can be set to delay recognition of
a contact input. By default, all inputs are configured so that they do not trigger an alarm or pre-alarm.
To make identifying the contact inputs easier, a user-assigned name
can be given to each input.
BESTCOMSPlus settings for the configurable contact inputs (DGC-2020, Programmable Inputs,
Configurable Inputs) are illustrated in Figure 4-18.