Winco DGC-2020 User Manual
Page 188

B-30 DGC-2020
Modbus
™ Communication
9400200990 Rev B
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
44552
Low Battery Pre-Alarm Threshold
120-240 for 24V
60-120 for 12V
R W
(Volts DC / 10) in increments of 1
44554
Low Battery Pre-Alarm Activation
Delay
1-10
R W
Seconds in increments of 1
44556
Weak Battery Pre-Alarm Enable
0-1
R W
0 = Disable
1 = Enable
44558
Weak Battery Pre-Alarm Threshold
80-160 for 24 V
40-80 for 12V
R W
(Volts DC / 10) in increments of 1
44560
Weak Battery Pre-Alarm Activation
Delay
1-10
R W
Seconds in increments of 1
44562
Battery Overvoltage Pre-Alarm
Enable
0-1 R
W
0 = Disable
1 = Enable
44564
Low Oil Press. Pre-Alarm Enable
0-1
R W
0 = Disable
1 = Enable
44566
Low Oil Press. Pre-Alarm
Threshold
3-150
R W
psi in increments of 1
44568
Metric Low Oil Press. Pre-Alarm
Threshold
25-1030
R W
kPa in increments of 1
44570
Engine Overload Pre-Alarm Enable
0-1
R W
0 = Disable
1 = Enable
44572
Engine Overload Pre-Alarm
Threshold
95-145
R W
% in increments of 1
44574
ECU Comms Fail Pre-Alarm
Enable
0-1 R
W
0 = Disable
1 = Enable
44576
Active DTC Pre-Alarm Enable
0-1
R W
0 = Disable
1 = Enable
44578
Maintenance Interval Pre-Alarm
Enable
0-1 R
W
0 = Disable
1 = Enable
44580
Maintenance Interval Pre-Alarm
Threshold
0-5000
R W
Hours in increments of 1
44582
Speed Sender Fail Activation Delay
0-300
R W
Seconds in increments of 1
44584
ECU Low Coolant Level Alarm
Enable
0-1 R
W
0 = Disable
1 = Enable
44586
ECU Low Coolant Level Alarm
Threshold
0-100
R W
% in increments of 1
44588
ECU Low Coolant Level Pre-Alarm
Enable
0-1 R
W
0 = Disable
1 = Enable
44590
ECU Low Coolant Level Pre-Alarm
Threshold
0-100
R W
% in increments of 1
44610-748 RESERVED
METERING
44750
Gen VAB Metering
0 - 4294967295
R
Volts in increments of 1
44752
Gen VBC Metering
0 - 4294967295
R
Volts in increments of 1
44754
Gen VCA Metering
0 - 4294967295
R
Volts in increments of 1
44756
Gen VAN Metering
0 - 4294967295
R
Volts in increments of 1
44758
Gen VBN Metering
0 - 4294967295
R
Volts in increments of 1
44760
Gen VCN Metering
0 - 4294967295
R
Volts in increments of 1
44762
Bus Voltage Metering
0 - 4294967295
R
Volts in increments of 1
44764
Gen IA Metering
0 - 4294967295
R
Amps in increments of 1
44766
Gen IB Metering
0 - 4294967295
R
Amps in increments of 1
44768
Gen IC Metering
0 - 4294967295
R
Amps in increments of 1
44770
Gen kVA A Metering
0 - 4294967295
R
kVA in increments of 1
44772
Gen kVA B Metering
0 - 4294967295
R
kVA in increments of 1
44774
Gen kVA C Metering
0 - 4294967295
R
kVA in increments of 1
44776
Gen kVA Total Metering
0 - 4294967295
R
kVA in increments of 1
44778
Gen kW A Metering
0 - 4294967295
R
kW in increments of 1
44780
Gen kW B Metering
0 - 4294967295
R
kW in increments of 1
44782
Gen kW C Metering
0 - 4294967295
R
kW in increments of 1
44784
Gen kW Total Metering
0 - 4294967295
R
kW in increments of 1
44786
Power Factor Metering
-1.00 to +1.00
R
FP
In increments of
0.01