Winco DGC-2020 User Manual
Page 169

9400200990 Rev B
DGC-2020 Modbus
™ Communication
B-11
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
40082 Alarm
Codes
individual bits
are 0 or 1
R -
b0=High Coolant Temperature
b1=Low Coolant Level
b2=Low Fuel Level
b3=Emergency Stop
b4=Sender Failure
b5=Over Crank
b6=Over Speed
b7=Low Oil Pressure
Rev. 3.04 Added:
b8 = CAN Fail
40083 Pre-Alarm
Codes
individual bits
are 0 or 1
R -
b0=High Coolant Temperature
b1=Low Coolant Temperature
b2=Weak Battery
b3=Low Battery
b4=Battery Overvoltage
b5=Battery Charger Fail
b6=Maintenance Interval
b7=Engine Overload
Rev. 3.04 Added:
b8 = DTC
b9 = CAN Fail
40084
Pre-Alarm Codes, Group 2
individual bits
are 0 or 1
R -
b0=Low Oil Pressure
b1=Low Fuel Level
b2=Magnetic Pick-up Fail
b3=Fuel Level Sender Fail
b4=Aux Input 1
b5=Aux Input 2
b6=Aux Input 3
b7=Aux Input 4
40085
Engine Coolant Temperature
R -
DegF
40086
Engine Oil Pressure
R -
PSI
40087
Battery Voltage
R -
.1 VoltsDC
40088
Fuel Level
R -
% Full Tank
40089
Time Remaining until Maintenance
R -
Hours
40090
Accumulated Engine Runtime(a)
R W
DP
Minutes x 10000
40091
Accumulated Engine Runtime(b)
R W
DP
Minutes
40092
Not Currently Used
R W
DP
40093
Not Currently Used
R W
DP
40094
Engine Speed(a)
R -
DP
RPM x10000
40095
Engine Speed(b)
R -
DP
RPM
40096
Engine Load(a)
R -
DP
40097
Engine Load(b)
R -
DP
% of Rated Load
GENERATOR MONITOR
40098
Phase a-b RMS Voltage(a)
R -
DP
RMS Volt x
10000
40099
Phase a-b RMS Voltage(b)
R -
DP
RMS Volt
40100
Phase b-c RMS Voltage(a)
R -
DP
RMS Volt x
10000
40101
Phase b-c RMS Voltage(b)
R -
DP
RMS Volt
40102
Phase c-a RMS Voltage(a)
R -
DP
RMS Volt x
10000
40103
Phase c-a RMS Voltage(b)
R -
DP
RMS Volt
40104
Phase a-n RMS Voltage(a)
R -
DP
RMS Volt x
10000
40105
Phase a-n RMS Voltage(b)
R -
DP
RMS Volt
40106
Phase b-n RMS Voltage(a)
R -
DP
RMS Volt x
10000
40107
Phase b-n RMS Voltage(b)
R -
DP
RMS Volt
40108
Phase c-n RMS Voltage(a)
R -
DP
RMS Volt x
10000
40109
Phase c-n RMS Voltage(b)
R -
DP
RMS Volt