Winco DGC-2020 User Manual
Page 186

B-28 DGC-2020
Modbus
™ Communication
9400200990 Rev B
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
44262
1 Phase Overcurrent Curve
0-16
R W
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
44264
1 Phase Overcurrent Alarm
Configuration
0-2 R
W
0 = None
1 = Alarm
2 = Pre-Alarm
44266
Phase Imbalance Pickup
5-100
R W
Volts in increments of 1
44268
Phase Imbalance Activation Delay
0-300
R W
(Seconds / 10) in increments of 1
44270
Phase Imbalance Alarm
Configuration
0-2 R
W
0 = None
1 = Alarm
2 = Pre-Alarm
44272
3 Phase Undervoltage Pickup
70-576
R W
Volts in increments of 1
44274
3 Phase Undervoltage Activation
Delay
0-300
R W
(Seconds / 10) in increments of 1
44276
3 Phase Undervoltage Inhibit
Frequency
20-400
R W
Hz in increments of 1
44278
3 Phase Undervoltage Alarm
Configuration
0-2 R
W
0 = None
1 = Alarm
2 = Pre-Alarm
44280
1 Phase Undervoltage Pickup
70-576
R W
Volts in increments of 1
44282
1 Phase Undervoltage Activation
Delay
0-300
R W
(Seconds / 10) in increments of 1
44284
1 Phase Undervoltage Inhibit
Frequency
20-400
R W
Hz in increments of 1
44286
1 Phase Undervoltage Alarm
Configuration
0-2 R
W
0 = None
1 = Alarm
2 = Pre-Alarm
44288
3 Phase Overvoltage Pickup
70-576
R W
Volts in increments of 1
44290
3 Phase Overvoltage Activation
Delay
0-300
R W
(Seconds / 10) in increments of 1
44292
3 Phase Overvoltage Alarm
Configuration
0-2 R
W
0 = None
1 = Alarm
2 = Pre-Alarm
44294
1 Phase Overvoltage Pickup
70-576
R W
Volts in increments of 1
44296
1 Phase Overvoltage Activation
Delay
0-300
R W
(Seconds / 10) in increments of 1
44298
1 Phase Overvoltage Alarm
Configuration
0-2 R
W
0 = None
1 = Alarm
2 = Pre-Alarm
44300 Underfrequency
Pickup
450-550 50Hz
540-660 60Hz
3600-4400
400Hz
R W
(Hz / 10) in increments of 1
44302
Underfrequency Activation Delay
0-300
R W
(Seconds / 10) in increments of 1
44304
Underfrequency Inhibit Voltage
70-576
R W
Volts in increments of 1
44306
Underfrequency Alarm
Configuration
0-2 R
W
0 = None
1 = Alarm
2 = Pre-Alarm