Current parameter table – Winco DGC-2020 User Manual
Page 182

B-24 DGC-2020
Modbus
™ Communication
9400200990 Rev B
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
40760 MDEC
Alarms
0-65535
R
b0 = High Charge Air Temp,
b1 = High Oil Temp,
b2 = High Coolant Temp,
b3 = Low Aftercooler Level,
b4 = Low Fuel Delivery Press,
b5 = Low Oil Press,
b6 = Overspeed,
b7 = Combined Red,
b8-b15 UNASSIGNED
40761 MDEC
Pre-alarms
0-65535
R
b0 = High ECU Temp,
b1 = High Oil Temp,
b2 = High Intercooler Temp,
b3 = High Charge Air Temp,
b4 = High Coolant Temp,
b5 = Shutdown Override,
b6 = High Fuel Rail Press,
b7 = Low Fuel Rail Press,
b8 = Low Coolant Level,
b9 = Low Charge Air Pressure,
b10 = Low Fuel Deliv Pressure,
b11 = Low Oil Pressure,
b12 = Combined Yellow,
b13-b15 UNASSIGNED
Current Parameter Table
The DGC-2020 maps all non-legacy parameters into the Holding Register address space (42000 and
above). Query address N will access the Holding Register N+1. Data Format is Long Integer type data
unless identified otherwise in the Data Format column. See Table B-4.
Table B-4. Current Parameter Table
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
BREAKER MANAGEMENT
42000
Gen Breaker Configured
0-1
R
0 = NOT Configured,
1 = Configured
42002
Gen Breaker Open Pulse Time
1-80
R W
milliseconds * 10
42004
Gen Breaker Close Pulse Time
1-80
R W
milliseconds * 10
42006
Gen Breaker Contact Type
0-1
R W
0 = Pulse,
1 = Continuous
42008
Gen Breaker Close Time
0-800
R W
milliseconds in increments of 5
42010 RESERVED
42012
Mains Breaker Configured
0-1
R W
0 = NOT Configured,
1 = Configured
42014
Mains Breaker Open Pulse Time
1-80
R W
milliseconds * 10
42016
Mains Breaker Close Pulse Time
1-80
R W
milliseconds * 10
42018
Mains Breaker Ouput Continuous
0-1
R W
0 = Pulse,
1 = Continuous
42020
Mains Breaker Close Time
0-800
R W
milliseconds in increments of 5
42022 RESERVED
42024 Synchronizer
Type
1-2
R
W
1 = Anticipatory,
2 = Phase Lock Loop
42026 RESERVED
42028
Slip Frequency
5-50
R W
(milliseconds * 10) in increments of 5
42030
Breaker Closing Angle
30-200
R W
Degrees / 10 in increments of 10
42032
Regulation Offset
20-150
R W
(% / 10) in increments of 5
42034
Vgen > Vbus
0-1
R W
0 = Disable
1 = Enable
42036
Fgen > Fbus
0-1
R W
0 = Disable
1 = Enable
42038-40 RESERVED