Time dial setting cross-reference – Winco DGC-2020 User Manual
Page 139

9400200990 Rev B
DGC-2020 Time Overcurrent Characteristic Curves
A-3
Table A-2. Characteristic Curve Cross-Reference
Curve Curve
Name
Drawing No.
Similar To
S1
S, S1, Short Inverse
99-1369
ABB CO-2
S2
S2, Short Inverse
99-1595
GE IAC-55
L1
L, L1, Long Inverse
99-1370
ABB CO-5
L2
L2, Long Inverse
99-1594
GE IAC-66
D
D, Definite Time
99-1371
ABB CO-6
M
M, Moderately Inverse
99-1372
ABB CO-7
I1
I, I1, Inverse Time
99-1373
ABB CO-8
I2
I2, Inverse Time
99-1597
GE IAC-51
V1
V, V1, Very Inverse
99-1374
ABB CO-9
V2
V2, Very Inverse
99-1596
GE IAC-53
E1
E, E1, Extremely Inverse
99-1375
ABB CO-11
E2
E2, Extremely Inverse
99-1598
GE IAC-77
A
A, Standard Inverse
99-1621
BS, IEC Standard Inverse
B
B, Very Inverse (I
2
t)
99-1376
BS, IEC Very Inverse (I
2
t)
C
C, Extremely Inverse (I
2
t)
99-1377
BS, IEC Extremely Inverse (I
2
t)
G
G, Long Time Inverse (I
2
t)
99-1622
BS, IEC Long Time Inverse (I
2
t)
F
Fixed Time
N/A
N/A
Time Dial Setting Cross-Reference
Although the time characteristic curve shapes have been optimized for the DGC-2020, the DGC-2020
time dial settings are not identical to the settings of electromechanical induction disk overcurrent relays.
Table A-3 helps you convert the time dial settings of induction disk relays to the equivalent setting for the
DGC-2020.
Using Table A-3
Cross-reference table values were obtained by inspection of published electromechanical time current
characteristic curves. The time delay for a current of five times tap was entered into the time dial
calculator function for each time dial setting. The equivalent DGC-2020 time dial setting was then entered
into the cross-reference table.
If your electromechanical relay time dial setting is between the values provided in the table, it will be
necessary to interpolate (estimate the correct intermediate value) between the electromechanical setting
and the Basler Electric setting.
The DGC-2020 has a maximum time dial setting of 9.9. The Basler Electric equivalent time dial setting for
the electromechanical maximum setting is provided in the cross-reference table even if it exceeds 9.9.
This allows interpolation as noted above.
Basler Electric time current characteristics are determined by a linear mathematical equation. The
induction disk of an electromechanical relay has a certain degree of non linearity due to inertial and
friction effects. For this reason, even though every effort has been made to provide characteristic curves
with minimum deviation from the published electromechanical curves, slight deviations can exist between
them.
In applications where the time coordination between curves is extremely close, we recommend that you
choose the optimal time dial setting by inspection of the coordination study. In applications where
coordination is tight, it is recommended that you retrofit your circuits with Basler Electric electronic relays
to ensure high timing accuracy.