Winco DGC-2020 User Manual
Page 187

9400200990 Rev B
DGC-2020 Modbus
™ Communication
B-29
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
44308 Overfrequency
Pickup
450-550 50Hz
540-660 60Hz
3600-4400
400Hz
R W
(Hz / 10) in increments of 1
44310
Overfrequency Activation Delay
0-300
R W
(Seconds / 10) in increments of 1
44312
Overfrequency Alarm Configuration
0-2
R W
0 = None
1 = Alarm
2 = Pre-Alarm
44314
Overcurrent Low Line Scale Factor
0.000 - 3.000
R W
FP
In increments of
0.001
44316
Overvoltage Low Line Scale Factor
0.000 - 3.000
R W
FP
In increments of
0.001
44318
Undervoltage Low Line Scale
Factor
0.000 - 3.000
R W
FP
In increments of
0.001
44320-498 FUTURE
USE
ALARMS
44500
High Coolant Temp Alarm Enable
0-1
R W
0 = Disable
1 = Enable
44502
High Coolant Temp Alarm
Threshold
100-280
R W
°F in increments of 1
44504
Metric High Coolant Temp Alarm
Threshold
37-137
R W
°C in increments of 1
44506
High Coolant Temp Alarm
Activation Delay
50-150
RW
Seconds in increments of 1
44508
Low Oil Press. Alarm Enable
0-1
R W
0 = Disable
1 = Enable
44510
Low Oil Press. Alarm Threshold
3-150
R W
psi in increments of 1
44512
Metric Low Oil Press. Alarm
Threshold
25-1030
R W
kPa in increments of 1
44514
Low Oil Press. Alarm Arming Delay
5-15
R W
Seconds in increments of 1
44516
Overspeed Alarm Enable
0-1
R W
0 = Disable
1 = Enable
44518
Overspeed Alarm Threshold
105-140
R W
% in increments of 1
44520
Overspeed Alarm Activation Delay
0-500
R W
Milliseconds in increments of 1
44522
Low Fuel Level Alarm Enable
0-1
R W
0 = Disable
1 = Enable
44524
Low Fuel Level Alarm Threshold
0-100
R W
% in increments of 1
44526
Low Fuel Level Alarm Activation
Delay
0-30
R W
Seconds in increments of 1
44528
High Coolant Temp Pre-Alarm
Enable
0-1 R
W
0 = Disable
1 = Enable
44530
High Coolant Temp Pre-Alarm
Threshold
100-280
R W
°F in increments of 1
44532
Metric High Coolant Temp Pre-
Alarm Threshold
37-137
R W
°C in increments of 1
44534
Low Coolant Temp Pre-Alarm
Enable
0-1 R
W
0 = Disable
1 = Enable
44536
Low Coolant Temp Pre-Alarm
Threshold
50-100
R W
°F in increments of 1
44538
Metric Low Coolant Temp Pre-
Alarm Threshold
10-37
R W
°C in increments of 1
44540
High Fuel Level Pre-Alarm
Threshold
0-100
R W
% in increments of 1
44542
High Fuel Level Pre-Alarm Enable
0-1
R W
0 = Disable
1 = Enable
44544
High Fuel Level Pre-Alarm
Activation Delay
0-30
R W
Seconds In increments of 1
44546
Low Fuel Level Pre-Alarm Enable
0-1
R W
0 = Disable
1 = Enable
44548
Low Fuel Level Pre-Alarm
Threshold
10-100
R W
% in increments of 1
44550
Low Battery Pre-Alarm Enable
0-1
R W
0 = Disable
1 = Enable