Modem setup (optional), Dial-out, Dial-in – Winco DGC-2020 User Manual
Page 62

4-12
DGC-2020 BESTCOMSPlus Software
9400200990 Rev B
A
Enable ECU Support: Check box to enable ECU support.
B
Enable DTC Support: Check box to enable DTC support.
C
CANBus Address: Accepts an address number from 0 to 253 in increments of 1.
D
ECU Config: Standard, Volvo Penta, or MTU MDEC.
E
Speed Select: Primary or Secondary.
F
Accelerator Position: Adjustable from 0 to 100% in 1% increments.
G
Select MDEC module type: Can Module 201, 302, 303, or 304.
H
MDEC speed demand switch: Analog CAN, Analog ECU, Up Down ECU, Up Down Can, Frequency, or
No CAN Demand.
I
MDEC engine RPM request: Adjustable from 1,400 to 2,000 in increments of 1.
J
Output Select: Fuel Contact or Pre-start Contact.
K
Pulsing: Enable or Disable.
L
Engine Shutdown: Adjustable from 1 to 60 s in 1 s increments.
M
Pulse Cycle Time: Adjustable from 1 to 60 s in 1 s increments.
N
Settling Time: Adjustable from 5,500 to 30,000 ms in 1 ms increments.
O
Response Timeout: Adjustable from 1 to 60 s in 1 s increments.
Modem Setup (Optional)
DGC-2020 controllers with style number xxxxxMxxx are equipped with an internal telephone modem that
has dial-in and dial-out capability. The modem gives the DGC-2020 the ability to dial up to four telephone
numbers
and annunciate user-selected conditions to specified pagers
. These user-selected conditions
include
:
• Auxiliary Input 1 Closed
• ECU Low Coolant Level Alarm
• Auxiliary Input 2 Closed
• Emergency Stop Alarm
• Auxiliary Input 3 Closed
• High Coolant Temp Pre-Alarm
• Auxiliary Input 4 Closed
• kW
Overload
Pre-Alarm
• Auxiliary Input 5 Closed
• Loss of ECU Coms Alarm
• Auxiliary Input 6 Closed
• Loss of Generator Voltage Sensing Alarm
• Auxiliary Input 7 Closed
• Low Battery Voltage Pre-Alarm
• Auxiliary Input 8 Closed
• Low Coolant Temp Pre-Alarm
• Auxiliary Input 9 Closed
• Low Fuel Alarm
• Auxiliary Input 10 Closed
• Low Fuel Pre-Alarm
• Auxiliary Input 11 Closed
• Low Oil Pressure Alarm
• Auxiliary Input 12 Closed
• Low Oil Pressure Pre-Alarm
• Auxiliary Input 13 Closed
• MPU Speed Sender Fail Alarm
• Auxiliary Input 14 Closed
• Oil Pressure Sender Fail Alarm
• Auxiliary Input 15 Closed
• Overcrank
Alarm
• Auxiliary Input 16 Closed
• Overspeed
Alarm
• Battery Overvoltage Pre-Alarm
• Scheduled Maintenance Pre-Alarm
• Coolant Temp Sender Fail Alarm
• Switch Not in Auto
• Cooldown Timer Active
• Weak Battery Voltage Pre-Alarm
Dial-Out
The DGC-2020 uses telelocator alphanumeric protocol (TAP) version 1.7 when communicating with
paging companies. This data format
specifies seven data bits with even parity. If required, eight data bits
with no parity may be specified.
The message string sent by the DGC-2020 can be limited to a length supported by the receiving pagers
.
If a message to be transmitted by the DGC-2020 exceeds the pager message limit, the DGC-2020 will
make multiple calls to transmit the complete message.
Dial-out messages are sent by the DGC-2020 at a user-defined interval
. This interval gives an operator
the opportunity to dial into the DGC-2020. A second user-defined interval
determines how frequently
dial-out attempts are made following a dial-out failure.
Dial-In
When the DGC-2020 modem shares a line used for voice communication, the number of rings
required
for the modem to answer can be increased to allow time for an operator to answer an incoming telephone
call.