Winco DGC-2020 User Manual
Page 184

B-26 DGC-2020
Modbus
™ Communication
9400200990 Rev B
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
42790
Bus Sensing Stable Overvoltage
Dropout
100-12000
R W
(Volts / 10) in increments of 10
42792
Bus Sensing Stable
Underfrequency Pickup
4600-6400
R W
(Hz / 100) in increments of 5
42794
Bus Sensing Stable
Underfrequency Dropout
4600-6400
R W
(Hz / 100) in increments of 5
42796
Bus Sensing Stable Overfrequency
Pickup
4600-6400
R W
(Hz / 100) in increments of 5
42798
Bus Sensing Stable Overfrequency
Dropout
4600-6400
R W
(Hz / 100) in increments of 5
42800
Bus Sensing Fail Time Delay
1-6000
R W
(milliseconds * 100) in increments of 1
42802
Bus Sensing Stable Time Delay
1-6000
R W
(milliseconds * 100) in increments of 1
42804 RESERVED
42806-3432 FUTURE
USE
SENDERS
43434
Coolant Temperature Sender Fail
Configuration Type
-1, 0, 1
R W
0 = None
1 = Alarm
2 = Pre-Alarm
43436
Coolant Temperature Sender Fail
Activation Delay
50-300
R W
Minutes in increments of 5
43438
Oil Pressure Sender Fail
Configuration Type
-1, 0, 1
R W
0 = None
1 = Alarm
2 = Pre-Alarm
43440
Oil Pressure Sender Fail Activation
Delay
0-300
R W
Seconds in increments of 1
43442
Fuel Level Sender Fail
Configuration Type
-1, 0, 1
R W
0 = None
1 = Alarm
2 = Pre-Alarm
43444
Fuel Level Sender Fail Activation
Delay
0-300
R W
Seconds in increments of 1
43446
Voltage Sensing Fail Configuration
Type
-1, 0, 1
R W
0 = None
1 = Alarm
2 = Pre-Alarm
43448
Voltage Sensing Fail Activation
Delay
0-300
R W
Seconds in increments of 1
43450-498 FUTURE
USE
SYSTEM CONFIGURATION AND STATUS
43500
Rated Volts
1-999
R W
Volts in increments of 1
43502
Pre-Start Contact Config
0-1
R W
0 = Open After Disconnect
1 = Closed While Running
43504
System Units
0-1
R W
0 = English
1 = Metric
43506
Battery Volts
0-1
R W
0 = 12V
1 = 24V
43508
Off Mode Status
0-1
R
0 = Disable
1 = Enable
43510
Run Mode Status
0-1
R
0 = Disable
1 = Enable
43512
Auto Mode Status
0-1
R
0 = Disable
1 = Enable
43514
Virtual Input 1 Status
0-1
R
0 = Disable
1 = Enable
43516
Virtual Input 2 Status
0-1
R
0 = Disable
1 = Enable
43518
Virtual Input 3 Status
0-1
R
0 = Disable
1 = Enable
43520
Virtual Input 4 Status
0-1
R
0 = Disable
1 = Enable
43522-748 FUTURE
USE
CONTROL
43750
Emergency Stop
0-1
R W
A value of 1 will invoke the Emergency
Stop