Winco DGC-2020 User Manual
Page 140

A-4
DGC-2020 Time Overcurrent Characteristic Curves
9400200990 Rev B
Table A-3 .Time Dial Setting Cross-Reference
Electromechanical Relay Time Dial Setting
0.5 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0
Curve
Equivalent
To
Drawing
Number
Basler Electric Equivalent Time Dial Setting
S, S1
ABB CO-2
99-1369
0.3
0.8
1.7 2.4 3.4 4.2 5.0 5.8 6.7 7.7 8.6 9.7
L, L1
ABB CO-5
99-1370
0.4
0.8
1.5 2.3 3.3 4.2 5.0 6.0 7.0 7.8 8.8 9.9
D
ABB CO-6
99-1371
0.5
1.1
2.0 2.9 3.7 4.5 5.0 5.9 7.2 8.0 8.9 10.1
M
ABB CO-7
99-1369
0.4
0.8
1.7 2.5 3.3 4.3 5.3 6.1 7.0 8.0 9.0 9.8
I, I1
ABB CO-8
99-1373
0.3
0.7
1.5 2.3 3.2 4.0 5.0 5.8 6.8 7.6 8.7 10.0
V, V1
ABB CO-9
99-1374
0.3
0.7
1.4 2.1 3.0 3.9 4.8 5.7 6.7 7.8 8.7 9.6
E, E1
ABB CO-11
99-1375
0.3
0.7
1.5 2.4 3.2 4.2 5.0 5.7 6.6 7.8 8.5 10.3
I2
GE IAC-51
99-1597
0.6
1.0
1.9
2.7
3.7 4.8 5.7 6.8 8.0 9.3 10.6
N/A
V2
GE IAC-53
99-1596
0.4
0.8
1.6
2.4
3.4 4.3 5.1 6.3 7.2 8.4 9.6 N/A
S2
GE IAC-55
99-1595
0.2
1.0
2.0
3.1
4.0 4.9 6.1 7.2 8.1 8.9 9.8 N/A
L2
GE IAC-66
99-1594
0.4
0.9
1.8
2.7
3.9 4.9 6.3 7.2 8.5 9.7 10.9
N/A
E2
GE IAC-77
99-1598
0.5
1.0
1.9
2.7
3.5 4.3 5.2 6.2 7.4 8.2 9.9 N/A